To change the other parameters (Second Level) follow these steps:
Step 1 |
| Press and hold SET and DOWN for 10 seconds. The display |
| and | will show dSPL |
|
| |
|
|
|
Step 2 |
| Press SET to change the parameter |
|
|
|
Step 3 |
| Press UP or DOWN to change the options, time or temperature |
| or | for the current parameter |
|
| |
|
|
|
Step 4 |
| Press SET to accept the new value |
|
|
|
Step 5 |
| Press DOWN to go to the next parameter, then go back to Step |
|
| 2. After the last parameter is displayed (ALHi), the display will |
|
| go back to the normal operating condition |
Note: to scroll down the parameters without changing them, press the DOWN button.
List of Parameters
Here is a list of the parameters that can be changed in the Second Level of programming, as well as their options and ranges.
Note:
Parameter | Displa | Description |
| Range / Options | Master- |
| y |
|
|
| Bilt’s |
| Symbo |
|
|
| Factory |
| l |
|
|
| Setting |
Display Status | dSPL | Information shown |
| tdAy – |
|
|
| on the display |
| rSP° – zone temperature | rSP |
|
| during operation |
| CyCL – cycle between time and |
|
|
| conditions |
| zone temperature |
|
|
|
|
| Epr° – evaporator coil temperature |
|
Clock Format | CLHr | Time Format(12 or |
| 12Hr – AM/PM format | 12Hr |
|
| 24 hours mode) |
| 24Hr – 24 hour format |
|
Temperature | °dSP | Temperature |
| °F – degrees Fahrenheit | °F |
Format |
| degrees |
| °C – degrees Celsius |
|
Defrost Type | dFtP | Type of defrost used |
| ELEC – electric defrost / off cycle | ELEC |
|
| in the application |
| HgAS – hot gas defrost |
|
Fan Status | EFAN | Enable or not the |
| no – fan is turned off during defrost | No – for LT |
During Defrost |
| fan during defrost |
| yES – fan remains on during defrost | |
Fan Status | CFAN | Enable or not fan during |
| on – fan on during normal mode | on |
During Normal |
| normal compressor |
| CyCP – fan cycles with compressor |
|
Mode |
| on/off mode |
|
|
|
Defrost | dFin | Type of defrost |
| TdAy – | |
Interval |
| interval |
| CPrn – compressor run time | |
|
|
|
| tdEF – temperature initiated defrost |
|
|
|
|
| ddEF – demand initiated defrost |
|
Minimum | CoFF | Minimum time that |
| Range: from 0 to 15 min | 2 min. |
Compressor |
| the compressor |
|
|
|
Off Time |
| remain turned off |
|
|
|
|
| 10 |
|
|