TOA Electronics SSDV-3328 Table C, Maximum Minimum Feet Meter, Table D + H1 Maximum Minimum

Page 18

VERTICAL VENT FIGURES/TABLES (CONTINUED)

 

 

Table C

 

 

 

 

 

 

 

 

 

 

 

H+H1 Maximum

H Maximum

V Minimum

 

feet

(meter)

feet

(meter)

feet

(meter)

 

 

 

 

 

 

 

 

 

5

(1.524)

2

(0.610)

1

(0.305)

 

 

10

(3.048)

4

(1.219)

2

(0.610)

 

 

 

 

 

 

 

 

 

 

 

15

(4.572)

6

(1.829)

3

(0.914)

 

 

 

 

 

 

 

 

 

 

20

(6.096)

8

(2.438)

4

(1.219)

 

 

 

 

 

 

 

 

 

 

 

V + V1

+ H + H1

= 40 feet (12.2 m) Max

 

 

 

 

H = 8 feet (2.438 meters) Max.

 

V1

 

H + H1 = 20 feet (6.096 meters) Max.

 

 

 

uWhen using Secure Flex, use Firestop / Spacer SF4.5VF vWhen using Secure Flex, use Firestop / Spacer SF4.5HF

Example: If 20 feet total (H+H1) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H+H1) horizontal run up to a maximum total horizontal run of 20 feet.

Figure 29 - Rear Vent - three elbows

H1

uCeiling Firestop / Spacer (SV4.5VF)

vWall Firestop/

Spacer (SV4.5HF)

uCeiling

Firestop / Spacer (SV4.5VF)

V

H

Table D

H + H1 Maximum

 

V Minimum

feet

 

(meter)

feet

 

(meter)

 

 

 

 

 

 

5

 

(1.524)

 

Elbow Only

 

 

 

 

 

5

 

(1.524)

1

 

(0.305)

 

 

 

 

 

 

10

 

(3.048)

2

 

(0.610)

15

 

(4.572)

3

 

(0.914)

 

 

 

 

 

 

20

 

(6.096)

4

 

(1.219)

 

 

 

 

 

 

 

H + H1 = 20 feet (6.096 m) Max.

 

V + V1 + H + H1 = 40 ft. (12.192 m) Max.

uWhen using Secure Flex, use Firestop / Spacer SF4.5VF vWhen using Secure Flex, use Firestop / Spacer SF4.5HF

Figure 30 - Top Vent - three elbows

Example: If 20 feet total (H+H1) horizontal vent run is needed,

then 4 feet minimum of (V) verti-

 

uCeiling

cal vent will be required.

 

 

 

Firestop / Spacer

This table shows a 1(V) to 5(H)

V1

(SV4.5VF)

ratio. For every 1 foot of (V)

 

 

vertical, you are allowed 5 feet

 

 

of (H+H1) horizontal run up to

 

 

a maximum total horizontal run

 

 

of 20 feet.

 

H

An elbow is acceptable as 1 foot

 

 

of vertical rise except where

 

 

an elbow is the only vertical

 

H1

component in the system. See

 

Figure 35.

vWall Firestop/

Spacer (SV4.5HF)

V

Horizontal (Outside Wall)

Termination System

Figure 31, and Figures 34 to 40 on Pages 21 to 23 and their associated Horizontal Vent Table illustrate the various horizontal venting configurations that are possible for use with these appliances. Secure Vent pipe applications are shown in these Figures; Secure Flex pipe may also be used. A Horizontal Vent Table sum- marizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.

Both of these horizontal vent systems terminate through an outside wall. Building Codes limit or prohibit terminating in specific areas. Refer to Figure 7 on Page 8 for location guidelines.

Secure Vent SV4.5 direct vent system compo- nents are unitized concentric pipe components featuring positive twist lock connection, (refer to Figure 20 on Page 15). All of the appli- ances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.

A. Plan the vent run -

Analyze the vent routing and determine the types and quantities of sections required 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181

mm)net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Make allow- ances for elbows as indicated in Figure 22.

Maintain a minimum 1" (25 mm) clearance to combustibles on the vertical sections. Clear- ances for the horizontal runs are; 3" (76 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.

18

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Image 18
Contents 700,043M REV. a 06/2008 OTL Report No -F-29-5Table of Contents Electronic Models ModelsSSDVT/R-3328 Natural and Propane Gas Model SeriesNew York City, New York MassachusettsMassachusetts Horizontal Vent Re- quirements SIT MillivoltCold Climate Insulation LocationManufactured Home Requirements Vertical Vent Termination Clearances Vent Termination ClearancesHorizontal Vent Termination Clearances Roof Pitch Feet= Clearance to service regulator vent outlet Feet 91cm Canadian Installation US InstallationMeter/regulator assembly Inches 30cmAppliance and Vent Clearances Minimum Clearances to CombustiblesWall Finishes / Surrounds / Mantels SpacersFraming Detailed Installation StepsTypical Installation Sequence Routing Gas LineTop View Front ViewRight Side View Schedule 40 / Black Iron Pipe Fireplace Framing specificationsProper Sizing of Gas Line Length feetThese fireplaces must be vented directly to the outside Install the Vent System General InformationInstallation of Vent Restrictor Select Venting System Horizontal or VerticalVertical Straight Installation Vertical Termination Systems RoofEffective Vent Length Vertical Offset Installation Attach vent components to each other10-1/2 267 mm 305 mm PitchIf the vent system extends more than 5 feet 267 mm 451 mmTable B Maximum Minimum Feet Meter Vertical Vent FIGURES/TABLES610 305 219 829 914 438 524 Elbow Only 305 048 610 572 914 096 219Meter 524 610 305 048 219 572 829 914 096 438 Table CMaximum Minimum Feet Meter Table D + H1 Maximum MinimumSee on Page 14 or on Install Firestop/Spacer at exterior wall Install the Square Termination SV4.5HT-2 or SF4.5HT-2See on Page 11 for Min Horizontal Vent FIGURES/TABLES Horizontal Vent Figures / Tables Square termination SV4.5HT-2 shown Flexible Vent Section Install the Outer Flex PipePull and extend outer flexible vent pipe Attach Flex Vent to TerminationSIT and Honeywell Millivolt Wiring Field WiringWiring Optional Forced Air Blower Kit See FigureConnecting Gas Line Schematic Representation OnlySIT and Honeywell Millivolt Appliance Checkout Reinstalling Control Compartment DoorChecking Appliance Opera- tion SIT Gas ValveInstall Logs, Volcanic Stone Electronic Appliance CheckoutGlowing Embers Firebox Accessories / Parts Glowing EmbersBurner Adjustments Flame Appearance and sooting Installing the Glass DoorInstalling Glass Enclosure Panels Air Shutter Adjustment GuidelinesFinishing Requirements Wall Details Burner Air Shutter Adjustment ProcedureHood Installation Refer to FigureCat. No Model Description Cat. No Closed Top Shroud Termination KitsListed Secure Vent Components Listed Secure Flex ComponentsModel Description All compressed flex vents can be expanded up to two timesSIT Millivolt Gas Valve Adjusting KnobMillivolt Appliances SIT Systems Pilot for SIT Millivolt Gas ValveIgnitor Assembly Flare Nut Clip

SSDV-3328 specifications

TOA Electronics SSDV-3328 is an advanced digital mixing amplifier designed to provide high-quality sound reinforcement for various applications, including commercial facilities, educational institutions, and public address systems. This versatile amplifier combines several key features and cutting-edge technologies to deliver exceptional audio performance and flexibility.

One of the standout characteristics of the SSDV-3328 is its robust power output. With a rating of 150 watts per channel, it is capable of driving a variety of speaker setups, ensuring that sound coverage is both powerful and consistent across large areas. This makes it an ideal choice for venues such as auditoriums, conference rooms, and exhibition halls.

The SSDV-3328 offers a unique blend of analog and digital input options, allowing seamless integration with various audio sources. It supports connectivity through balanced XLR inputs, RCA, and even digital input formats, providing users with the capabilities needed to connect microphones, musical instruments, and playback devices. This flexibility is invaluable for professionals who require adaptable solutions for different audio setups.

Equipped with TOA's advanced DSP (Digital Signal Processing) technology, the amplifier provides enhanced audio quality and control. Users can benefit from features such as graphic equalization, delay settings, and limiting, which enable precise tuning of the audio output to match the acoustics of any space. This capability ensures that the audio remains clear and intelligible, regardless of the complexity of the setup.

Another noteworthy feature of the SSDV-3328 is its built-in feedback suppression technology, designed to minimize feedback issues that can occur in live sound situations. This not only enhances the listening experience but also reduces the workload on sound technicians during events.

The design of the SSDV-3328 emphasizes reliability and ease of use. Its intuitive control panel includes well-organized knobs and switches for quick adjustments, while status indicators provide real-time feedback on system performance. Additionally, the lightweight and compact construction of the amplifier makes it easy to transport and install, meeting the demands of both permanent installations and portable setups.

In summary, TOA Electronics SSDV-3328 stands out in the realm of digital mixing amplifiers, offering powerful output, versatile connectivity, advanced DSP features, and a commitment to audio quality. Whether used in commercial spaces or live events, this amplifier is designed to deliver performance that meets the highest standards in sound reinforcement. Its thoughtful design and innovative technologies make it a reliable choice for audio professionals seeking a top-tier mixing amplifier.