TOA Electronics SSDV-3328 Checking Appliance Opera- tion, SIT Gas Valve, Piezo Igniter

Page 27

TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD):

WARNING

Never use an open flame to check for leaks.

Turn on gas supply and test for gas leaks using a gas leak test solution (also referred to as bubble leak solution). Note: Using a soapy water solution (50% dish soap, 50% water) is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/fittings can result in corrosion over time.

A. Light the appliance (refer to the lighting instructions label in control compartment or homeowner's manual).

B. Brush all joints and connections with the gas leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob (off/pilot/on) to the “OFF” position. Either tighten or refasten the leaking connection, then retest as described above.

C.When the gas lines are tested and leak free be sure to rinse off the leak testing solution,

D.Turn on burner then observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.

CONTROL COMPARTMENT ACCESS/ LOUVER PANEL INSTRUCTIONS (Ref. Figure 47)

NOTE: The top louvered panel and the bottom louvered control panel door remove and install the same way as follows:

The gas controls can be found behind the control compartment access door.

Removing Control Compartment Door: Open the door by gently lifting it upward until the hook catches on boths sides clear the locating slots. Then pull door out to remove.

On millivolt systems, the piezo igniter, HI/LO flame adjustment knob, and pilot and main gas OFF/ON control knob are located below the glass panel enclosure. The gas valve for electronic systems is also located below the glass enclosure panel. See Figure 47.

Reinstalling Control Compartment Door:

To reinstall, insert the hook catches on each side of the door into the corresponding slots in the control compartment opening, then gently push forward and slide down until it locks in place.

 

Lift the Lower Control

 

Compartment Door

OPENING CONTROL

up and pull out to

COMPARTMENT DOOR

remove.

 

Hook Catch

Control Valve

Out

 

Up

 

 

Lower Control

 

Compartment Door

Figure 47

Step 7. Checking Appliance Opera- tion

With the gas line installed, run initial system checkout before closing up the front of the appliance. Follow the pilot lighting instructions provided in the Homeowner's Care and Opera- tion Instructions. For piezo igniter location see Figure 48 (millivolt appliances only).

Note: The (pull-out) Lighting instructions label can be found in the control compartment (see Figure 47).

When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lightings of the appliance will not require such purging. Inspect the pilot flame.

SIT and Honeywell Millivolt Appliance Checkout

The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

The top 3/8" (10 mm) at the pilot generator (thermopile) and the top 1/8" min (tip) of the quick drop out thermocouple should be engulfed in the pilot flame. The flame should project 1" (25

mm)beyond the hood at all three ports (Figure 49 - SIT, Figure 50 - Honeywell).

To light the burner; rotate the gas valve control knob counterclockwise to the “ON” position then turn “ON” the OFF/ON switch (installed at Step 4).

Observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.

SIT Gas Valve

Honeywell

Gas Valve

Piezo

Igniter

Sit and Honeywell Millivolt Gas Valve

Showing Piezo Igniter Location (Each Unit is Equipped with Only One of these Gas Valves)

Figure 48

SIT MILLIVOLT PILOT ASSEMBLY

Proper Pilot Flame Appearance

Hood

Igniter Rod

Thermocouple

3/8" Min.

 

 

(9 mm)

Pilot

 

Nozzels

 

Thermopile

 

Figure 49

 

27

Image 27
Contents OTL Report No -F-29-5 700,043M REV. a 06/2008Table of Contents Natural and Propane Gas Model Series ModelsSSDVT/R-3328 Electronic ModelsSIT Millivolt MassachusettsMassachusetts Horizontal Vent Re- quirements New York City, New YorkLocation Cold Climate InsulationManufactured Home Requirements Roof Pitch Feet Vent Termination ClearancesHorizontal Vent Termination Clearances Vertical Vent Termination ClearancesInches 30cm Canadian Installation US InstallationMeter/regulator assembly = Clearance to service regulator vent outlet Feet 91cmSpacers Minimum Clearances to CombustiblesWall Finishes / Surrounds / Mantels Appliance and Vent ClearancesRouting Gas Line Detailed Installation StepsTypical Installation Sequence FramingTop View Front ViewRight Side View Length feet Fireplace Framing specificationsProper Sizing of Gas Line Schedule 40 / Black Iron PipeSelect Venting System Horizontal or Vertical Install the Vent System General InformationInstallation of Vent Restrictor These fireplaces must be vented directly to the outsideVertical Straight Installation Vertical Termination Systems RoofEffective Vent Length Attach vent components to each other Vertical Offset Installation267 mm 451 mm PitchIf the vent system extends more than 5 feet 10-1/2 267 mm 305 mm524 Elbow Only 305 048 610 572 914 096 219 Vertical Vent FIGURES/TABLES610 305 219 829 914 438 Table B Maximum Minimum Feet MeterTable D + H1 Maximum Minimum Table CMaximum Minimum Feet Meter Meter 524 610 305 048 219 572 829 914 096 438See on Page 14 or on Install Firestop/Spacer at exterior wall Install the Square Termination SV4.5HT-2 or SF4.5HT-2See on Page 11 for Min Horizontal Vent FIGURES/TABLES Horizontal Vent Figures / Tables Square termination SV4.5HT-2 shown Attach Flex Vent to Termination Install the Outer Flex PipePull and extend outer flexible vent pipe Flexible Vent SectionSee Figure Field WiringWiring Optional Forced Air Blower Kit SIT and Honeywell Millivolt WiringSchematic Representation Only Connecting Gas LineSIT Gas Valve Reinstalling Control Compartment DoorChecking Appliance Opera- tion SIT and Honeywell Millivolt Appliance CheckoutInstall Logs, Volcanic Stone Electronic Appliance CheckoutGlowing Embers Glowing Embers Firebox Accessories / PartsAir Shutter Adjustment Guidelines Installing the Glass DoorInstalling Glass Enclosure Panels Burner Adjustments Flame Appearance and sootingRefer to Figure Burner Air Shutter Adjustment ProcedureHood Installation Finishing Requirements Wall DetailsCat. No Model Description Closed Top Shroud Termination Kits Cat. NoAll compressed flex vents can be expanded up to two times Listed Secure Flex ComponentsModel Description Listed Secure Vent ComponentsPilot for SIT Millivolt Gas Valve Adjusting KnobMillivolt Appliances SIT Systems SIT Millivolt Gas ValveFlare Nut Clip Ignitor Assembly

SSDV-3328 specifications

TOA Electronics SSDV-3328 is an advanced digital mixing amplifier designed to provide high-quality sound reinforcement for various applications, including commercial facilities, educational institutions, and public address systems. This versatile amplifier combines several key features and cutting-edge technologies to deliver exceptional audio performance and flexibility.

One of the standout characteristics of the SSDV-3328 is its robust power output. With a rating of 150 watts per channel, it is capable of driving a variety of speaker setups, ensuring that sound coverage is both powerful and consistent across large areas. This makes it an ideal choice for venues such as auditoriums, conference rooms, and exhibition halls.

The SSDV-3328 offers a unique blend of analog and digital input options, allowing seamless integration with various audio sources. It supports connectivity through balanced XLR inputs, RCA, and even digital input formats, providing users with the capabilities needed to connect microphones, musical instruments, and playback devices. This flexibility is invaluable for professionals who require adaptable solutions for different audio setups.

Equipped with TOA's advanced DSP (Digital Signal Processing) technology, the amplifier provides enhanced audio quality and control. Users can benefit from features such as graphic equalization, delay settings, and limiting, which enable precise tuning of the audio output to match the acoustics of any space. This capability ensures that the audio remains clear and intelligible, regardless of the complexity of the setup.

Another noteworthy feature of the SSDV-3328 is its built-in feedback suppression technology, designed to minimize feedback issues that can occur in live sound situations. This not only enhances the listening experience but also reduces the workload on sound technicians during events.

The design of the SSDV-3328 emphasizes reliability and ease of use. Its intuitive control panel includes well-organized knobs and switches for quick adjustments, while status indicators provide real-time feedback on system performance. Additionally, the lightweight and compact construction of the amplifier makes it easy to transport and install, meeting the demands of both permanent installations and portable setups.

In summary, TOA Electronics SSDV-3328 stands out in the realm of digital mixing amplifiers, offering powerful output, versatile connectivity, advanced DSP features, and a commitment to audio quality. Whether used in commercial spaces or live events, this amplifier is designed to deliver performance that meets the highest standards in sound reinforcement. Its thoughtful design and innovative technologies make it a reliable choice for audio professionals seeking a top-tier mixing amplifier.