How to Use the Vent Graph

The vent chart should be read in conjunction with the following vent installation instructions to determine the relationship of the vertical and horizontal dimensions of the vent system.

1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 14) locate the point intersecting with slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fireplace in accordance with same.

Example A:

If the vertical dimension from the floor of the fireplace is 11’ (3.4 m) the horizontal run to the face of the outer wall must not exceed 14’ (4.3 m).

Example B:

If the vertical dimension from the floor of the unit is 7’ (2.14 m), the horizontal run to the face of the outer wall must not exceed 8¹⁄₂’ (2.6 m).

30

 

 

 

 

 

 

29

 

 

 

 

 

 

28

 

 

 

 

 

 

27

 

 

 

 

 

 

26

 

 

 

 

 

 

25

 

 

Vertical

 

 

24

 

tothe

 

23

 

 

 

 

22

 

 

 

 

 

 

21

 

center of thehorizontalventpipe

dimension fromtheflooroftheunit

 

7

 

20

 

 

 

19

 

 

 

18

 

 

 

17

 

 

 

16

 

 

 

15

 

 

 

14

 

 

 

13

 

 

 

eg: A

 

 

12

 

 

11

 

 

 

 

 

 

10

 

 

 

 

 

 

9

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

6

eg: B

 

 

 

 

5

 

 

 

 

 

 

4

 

 

 

 

 

 

3

 

 

 

 

 

 

�������� ����� ����������������������������������������������������������������

Horizontal dimension from the outside face of the

wall to the center of the fireplace vent flange

Sidewall vent graph showing the relationship between vertical

and horizontal dimensions for a Direct Vent flue system.

Fig. 14 Sidewall venting graph. (Dimensions in feet)

Vermont Castings DVR28 Direct Vent Gas Fireplace

Rear Wall Venting Applications

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance.

Only CFM Corporation venting components are approved to be used in these applications. (Refer to “Venting Components” listed for different installation requirements)

The maximum horizontal distance between the rear of the appliance (or end of the transition elbow in a corner application) and the outside face of the rear wall is 20” (508 mm). (Fig. 15 & 16)

Only one 45° elbow is allowed in these installations.

If using a 45° elbow at fireplace, you must start out using an 8” (203 mm) or 12” (305 mm) sec- tion of pipe first attached to heater then a 45° elbow.

Minimum clearances between vent pipe and com- bustible materials are as follows:

Top - 2” (51 mm)

Sides - 1” (25 mm)

Bottom - 1” (25 mm)

20”

(508 mm)

Max.

Rear Vent Top View

FP1780

Fig. 15 Rear vent application, no elbows.

20”

20”

(508 mm)

(508 mm)

Max.

Max.

45°

45°

 

Start with 8” (203 mm) or 12”

FP1779

(305 mm) Pipe Section

Fig. 16 Rear vent application, one 45° elbow.

20012301

11

Image 11
Contents Direct Vent Model DVR28IN Table of Contents Ansi Z21.88-2005 / CSA Vented Gas Fireplace Heaters Installation & Operating InstructionsCertified To Fireplace specifications and framing dimensions DVR28 Fireplace DimensionsClearance to Combustibles Installation Instructions PreparationLocating Your Fireplace Mounting the FireplaceHigh Elevations Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresInstallation Restrictor Plate InstallationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2Twist Lock Pipes Canadian InstallationsUSA Installations General Information Assembling Vent PipesExample B How to Use the Vent GraphRear Wall Venting Applications Example aZero clearance sleeve is only required for combustible walls Rear Wall Installation Twist Lock PipeTotal angular variation = Vertical Sidewall ApplicationsVertical Through-the-Roof Application Below Grade InstallationsPlace firestop spacers and secure Vertical Through-the-Roof InstallationMinimum termination to roof clearance Venting Components Glass Information Window Frame Assembly RemovalGlass Cleaning Operating InstructionsInspecting the Venting System Flame & Temperature AdjustmentFlame Characteristics Turning Off the Gas to the Appliance Lighting & Operating InstructionsFor Fireplaces equipped with AF4000 Gas Valve Lighting InstructionsAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveTroubleshooting AF4000 Valve Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Fireplace May Be HOTDVR28 DescriptionModel # Color Optional AccessoriesCurve Face Kit Screen Door KitLimited Lifetime Warranty 67.6 64.3 Efficiency Ratings