How to Use the Vent Graph
The vent chart should be read in conjunction with the following vent installation instructions to determine the relationship of the vertical and horizontal dimensions of the vent system.
1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 14) locate the point intersecting with slanted graph line.
2.From the point of this intersection, draw a vertical line to the bottom of the graph.
3.Select the indicated dimension, and position the fireplace in accordance with same.
Example A:
If the vertical dimension from the floor of the fireplace is 11’ (3.4 m) the horizontal run to the face of the outer wall must not exceed 14’ (4.3 m).
Example B:
If the vertical dimension from the floor of the unit is 7’ (2.14 m), the horizontal run to the face of the outer wall must not exceed 8¹⁄₂’ (2.6 m).
30 |
|
|
|
|
|
| |
29 |
|
|
|
|
|
| |
28 |
|
|
|
|
|
| |
27 |
|
|
|
|
|
| |
26 |
|
|
|
|
|
| |
25 |
|
| Vertical |
|
| ||
24 |
| tothe | |
| |||
23 |
| ||
|
|
| |
22 |
|
|
|
|
|
| |
21 |
| center of thehorizontalventpipe | dimension fromtheflooroftheunit |
| |||
7 |
| ||
20 |
|
|
|
19 |
|
|
|
18 |
|
|
|
17 |
|
|
|
16 |
|
|
|
15 |
|
|
|
14 |
|
|
|
13 |
|
|
|
eg: A |
|
| |
12 |
|
| |
11 |
|
|
|
|
|
| |
10 |
|
|
|
|
|
| |
9 |
|
|
|
|
|
| |
8 |
|
|
|
|
|
| |
|
|
|
|
6 | eg: B |
| |
|
|
| |
5 |
|
|
|
|
|
| |
4 |
|
|
|
|
|
| |
3 |
|
|
|
|
|
|
�������� ����� ����������������������������������������������������������������
Horizontal dimension from the outside face of the
wall to the center of the fireplace vent flange
Sidewall vent graph showing the relationship between vertical
and horizontal dimensions for a Direct Vent flue system.
Fig. 14 Sidewall venting graph. (Dimensions in feet)
Vermont Castings DVR28 Direct Vent Gas Fireplace
Rear Wall Venting Applications
When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance.
•Only CFM Corporation venting components are approved to be used in these applications. (Refer to “Venting Components” listed for different installation requirements)
•The maximum horizontal distance between the rear of the appliance (or end of the transition elbow in a corner application) and the outside face of the rear wall is 20” (508 mm). (Fig. 15 & 16)
•Only one 45° elbow is allowed in these installations.
•If using a 45° elbow at fireplace, you must start out using an 8” (203 mm) or 12” (305 mm) sec- tion of pipe first attached to heater then a 45° elbow.
•Minimum clearances between vent pipe and com- bustible materials are as follows:
Top - 2” (51 mm)
Sides - 1” (25 mm)
Bottom - 1” (25 mm)
20”
(508 mm)
Max.
Rear Vent Top View
FP1780
Fig. 15 Rear vent application, no elbows.
20” | 20” |
(508 mm) | (508 mm) |
Max. | Max. |
45° | 45° |
| Start with 8” (203 mm) or 12” |
FP1779 | (305 mm) Pipe Section |
Fig. 16 Rear vent application, one 45° elbow.
20012301 | 11 |