A minimum of an 8’ (2.5m) vertical rise is required.

Two sets of 45° elbow offsets may be used within the vertical sections. From 0 to a maximum of 8’ (2.5 m) of vent pipe can be used between elbows. (Fig. 26)

7DVCS supports offsets. (Fig. 28) This application will require that you first determine the roof pitch and use the appropriate starter kit. (Refer to Venting Components List)

The maximum angular variation allowed in the sys- tem is 270°. (Fig. 26)

The minimum height of the vent above the highest point of penetration through the roof is 2’ (610 mm). (Fig. 29)

1 + 2 + 3 + 4 = 270°

1

2

3

4

FP1179

Fig. 26 Maximum elbow usage.

Vertical Through-the-Roof Installation

1.Locate your fireplace.

2.Plumb to center of the (4”) flue collar from ceiling above and mark position.

3.Cut opening equal to 9³⁄” x 9³⁄” (240 x 240 mm).

4.Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1 inch clearance to the vent pipe, i.e., the hole must be at least 9³⁄” x 9³⁄” (240 x 240 mm).

5.Place fireplace into position.

6.Place firestop(s) #7DVFS or Attic Insulation Shield #7DVAIS into position and secure. (Fig. 27)

7.Install roof support (Fig. 44) and roof flashing making sure upper flange is below the shingles. (Fig. 28)

8.Install appropriate pipe sections until the venting is above the flashing. (Fig. 30)

9.Install storm collar and seal around the pipe.

10.Add additional vent lengths for proper height. (Fig. 29)

11.Apply high temperature sealant to 4” and 7” collars of vertical vent termination and install.

Vermont Castings DVR28 Direct Vent Gas Fireplace

If there is a room above ceiling level, fire stop spacer must be installed on both the bottom ad the top side of the ceiling joists. If an attic is above ceiling level a 7DVAIS (Attic Insulation Shield) must be installed.

The enlarged ends of the vent section always face downward.

Attic Insulation Shield

Upper Floor

11”

11”

(279mm)

(279mm)

 

Ceiling Installation

Joist

 

 

Firestop

 

Spacer

Nails (4)

FP1029

 

Fig. 27 Place firestop spacer(s) and secure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Typical Roof

 

 

 

 

 

 

 

 

 

 

Support

Typical Ceiling

Application

 

Support

 

 

 

Application

 

 

 

 

 

 

 

FP1184

 

 

 

 

 

 

 

 

Fig. 28 Venting supports.

 

 

 

 

 

20012301

15

Image 15
Contents Direct Vent Model DVR28IN Table of Contents Installation & Operating Instructions Certified ToAnsi Z21.88-2005 / CSA Vented Gas Fireplace Heaters Fireplace specifications and framing dimensions DVR28 Fireplace DimensionsClearance to Combustibles Installation Instructions PreparationLocating Your Fireplace Mounting the FireplaceHigh Elevations Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresInstallation Restrictor Plate InstallationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2Twist Lock Pipes Canadian InstallationsUSA Installations General Information Assembling Vent PipesExample B How to Use the Vent GraphRear Wall Venting Applications Example aZero clearance sleeve is only required for combustible walls Rear Wall Installation Twist Lock PipeTotal angular variation = Vertical Sidewall ApplicationsVertical Through-the-Roof Application Below Grade InstallationsPlace firestop spacers and secure Vertical Through-the-Roof InstallationMinimum termination to roof clearance Venting Components Glass Information Window Frame Assembly RemovalGlass Cleaning Operating InstructionsFlame & Temperature Adjustment Flame CharacteristicsInspecting the Venting System Turning Off the Gas to the Appliance Lighting & Operating InstructionsFor Fireplaces equipped with AF4000 Gas Valve Lighting InstructionsAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveTroubleshooting AF4000 Valve Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Fireplace May Be HOTDVR28 DescriptionModel # Color Optional AccessoriesCurve Face Kit Screen Door KitLimited Lifetime Warranty 67.6 64.3 Efficiency Ratings