Vermont Casting DVR28IN General Information Assembling Vent Pipes, Twist Lock Pipes

Page 10

Vermont Castings DVR28 Direct Vent Gas Fireplace

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside Corner

Outside Corner

Alcove Applications*

 

 

 

F =

 

 

G =

 

Combustible

G

Combustible

 

6"

(152 mm)

 

6" (152 mm)

V

Noncombustible

 

 

2"

(51 mm)

 

Noncombustible

 

V

 

F

 

2" (51 mm)

 

 

Balcony -

Balcony -

with no side wall

with perpendicular side wall

M

M

 

V

V

 

P

M =

Combustible &

Noncombustible

Combustible &

M = 24" (610 mm)

Noncombustible

P = 20” (508 mm)

12" (305 mm)

D

C C

V

E

O

E = Min. 6” (152 mm) for non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls

O = 8’ (2.4 m) Min.

No.

 

 

of Caps

DMin.

CMax.

1

3’ (914 mm)

2 x DActual

2

6’ (1.8 m)

1 x DActual

3

9’ (2.7 m)

2/3 x DActual

4

12’ (3.7 m)

1/2 x DActual

DMin. = # of Termination caps x 3

CMax. = (2 / # termination caps) x DActual

584-15

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.

Fig. 12 Termination clearances.

General Information Assembling Vent Pipes

Canadian Installations:

Venting system must be installed in accordance with the current CSA-B149.1 installation code.

USA Installations:

The venting system must conform with local codes and/ or the current National Fuel Gas code ANSI Z223.1/ NFPA 54.

Only venting components manufactured by CFM Corpo- ration can be used in Direct Vent systems.

Twist Lock Pipes

When using CFM Corporation twist-lock pipe it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high temperature silicone sealant are the sliding joints of any telescopic vent section used in the system.

To join the twist lock pipes together, simply align the beads of the male end with the grooves of the female end, then while bringing the pipe together, twist the pipe

until the flange on the female end contacts the external flange on the male end. It is recommended that you secure the joints with three (3) sheet metal screws, however this is not mandatory with twist lock pipe.

To make it easier to assemble the joints we suggest putting a lubricant (Vaseline or similar) on the male end of the twist lock pipe prior to assembly.

Male End

Female End

Screw Holes

TWL100

Fig. 13 Twist-lock pipe joints.

10

20012301

Image 10
Contents Direct Vent Model DVR28IN Table of Contents Certified To Installation & Operating InstructionsAnsi Z21.88-2005 / CSA Vented Gas Fireplace Heaters DVR28 Fireplace Dimensions Fireplace specifications and framing dimensionsMounting the Fireplace Installation Instructions PreparationLocating Your Fireplace Clearance to CombustiblesGas Inlet and Manifold Pressures Gas Line InstallationGas Specifications High ElevationsRestrictor Plate Installation InstallationGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationGeneral Information Assembling Vent Pipes Canadian InstallationsUSA Installations Twist Lock PipesExample a How to Use the Vent GraphRear Wall Venting Applications Example BRear Wall Installation Twist Lock Pipe Zero clearance sleeve is only required for combustible wallsVertical Sidewall Applications Total angular variation =Below Grade Installations Vertical Through-the-Roof ApplicationVertical Through-the-Roof Installation Place firestop spacers and secureMinimum termination to roof clearance Venting Components Operating Instructions Window Frame Assembly RemovalGlass Cleaning Glass InformationFlame Characteristics Flame & Temperature AdjustmentInspecting the Venting System Lighting Instructions Lighting & Operating InstructionsFor Fireplaces equipped with AF4000 Gas Valve Turning Off the Gas to the ApplianceTroubleshooting AF4000 ValveTroubleshooting AF4000 Valve Igniter operationTroubleshooting AF4000 Valve Fireplace May Be HOT MaintenanceCleaning the Standing Pilot Control System Burner and Burner CompartmentDescription DVR28Screen Door Kit Optional AccessoriesCurve Face Kit Model # ColorLimited Lifetime Warranty Efficiency Ratings 67.6 64.3