Vermont Castings DVR28 Direct Vent Gas Fireplace

Troubleshooting AF4000 Valve (continued)

Pilot flame is always on/ will

Ensure the CONTINUOUS PILOT switch on the control module (Fig. 36) is set

not extinguish

to OFF.

Main flame will not light

Verify the gas supply is turned on.

Ensure the pilot flame will ignite. If not, see pilot flame troubleshooting above.

 

 

Make sure the green and white leads from the module are securely connected to

 

the terminals labeled “MAIN: on the valve body. (Fig. 41)

 

Make certain the pilot flame is in contact with the flame rectification sensor on

 

the pilot assembly. This valve is equipped with a pilot flame adjustment screw.

 

(Fig. 41) If the pilot flame is too small it will not contact the flame rectification

 

sensor and will not complete the safety circuit.

 

Ensure the pilot flame is properly located to ignite the main flame.

Flame height adjustment will not work/works backwards

Ensure the black and red leads from the battery pack or the AF4000 110H/L module are securely connected to the red and black leads from the motor drive or H/L latching solenoid located on the valve body (red to red and black to black).

Verify the selector switch on the battery pack is set to DC MOTOR DRIVE or LATCHING SOLENOID, depending upon which device is installed. (Fig. 40)

Check functionality with all transmitters to determine if there is an issue with the main control system or an individual transmitter. If the issue is with an individual transmitter, make sure the batteries in both the transmitter and receiver are in- stalled in the proper direction (Fig. 39, 40) and are not drained. Individual battery voltage should be no less than 1.4V for AA and AAA batteries, 2.8V for button cells, and 9.0V for 12V batteries.

Figure 40: Battery Pack - Battery Compartment

 

 

+

Selector Switch

Drive

-

/ DC Motor

 

+

 

Solenoid

 

-

 

Latching

 

 

Figure 41: AF4000 Valve Face

Main Connection

MAIN

Inlet

Pilot Adj.

PILOT

Outlet

Pilot Connection

FP1767

FP1769

20012301

23

Image 23
Contents Direct Vent Model DVR28IN Table of Contents Ansi Z21.88-2005 / CSA Vented Gas Fireplace Heaters Installation & Operating InstructionsCertified To Fireplace specifications and framing dimensions DVR28 Fireplace DimensionsClearance to Combustibles Installation Instructions PreparationLocating Your Fireplace Mounting the FireplaceHigh Elevations Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresInstallation Restrictor Plate InstallationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2Twist Lock Pipes Canadian InstallationsUSA Installations General Information Assembling Vent PipesExample B How to Use the Vent GraphRear Wall Venting Applications Example aZero clearance sleeve is only required for combustible walls Rear Wall Installation Twist Lock PipeTotal angular variation = Vertical Sidewall ApplicationsVertical Through-the-Roof Application Below Grade InstallationsPlace firestop spacers and secure Vertical Through-the-Roof InstallationMinimum termination to roof clearance Venting Components Glass Information Window Frame Assembly RemovalGlass Cleaning Operating InstructionsInspecting the Venting System Flame & Temperature AdjustmentFlame Characteristics Turning Off the Gas to the Appliance Lighting & Operating InstructionsFor Fireplaces equipped with AF4000 Gas Valve Lighting InstructionsAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveTroubleshooting AF4000 Valve Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Fireplace May Be HOTDVR28 DescriptionModel # Color Optional AccessoriesCurve Face Kit Screen Door KitLimited Lifetime Warranty 67.6 64.3 Efficiency Ratings