Orion 2xx manual Analog Input Block, Channels, Firmware Version, AI Block Parameters

Page 18

Probe Mount

100% Set Point

Probe Model

Probe Length

0% Set Point

Level Offset

Scaling

3.4.2Firmware Version

The last two parameters in the TRANSDUCER block show the firmware version of the transmitter.

FIRMWARE_VERSION: displays the version of the firmware.

COPROCESSOR_VERSION: displays the version of the coprocessor.

3.5Analog Input Block

The ANALOG INPUT (AI) block takes the transducer blocks input data, selected by channel number, and makes it available to other function blocks at its output:

Channels

1.Level

2.Interface Level

3.5.1AI Block Parameters

PV: Either the primary analog value for use in executing the function, or a process value associated with it.

OUT: The primary analog value calculated as a result of executing the function block.

SIMULATE: Allows the transducer analog input or output to the block to be manually supplied when simulate is enabled. When simulate is disabled, the simulate value and status track the actual value and status

XD_SCALE: The high and low scale values, engineering units code, and number of digits to the right of the decimal point used with the value obtained from the transducer for a specified channel.

OUT_SCALE: The high and low scale values, engineering units code, and number of digits to the right of the decimal point to be used in displaying the OUT parameter.

GRANT_DENY: Options for controlling access of host computers and local control panels to operating, tuning, and alarm parameters of the block.

IO_OPTS: Option which the user may select to alter input and output block processing.

STATUS_OPTS: Options which the user may select in the block processing of status.

15

46-649 Jupiter Magnetostrictive Transmitter - FOUNDATION fieldbus™

Image 18
Contents Magnetostrictive Level Transmitter Read this Manual Before Installing Table of Contents Foundation Fieldbus Overview DescriptionDevice Configuration Device Descriptions BenefitsIntrinsic Safety Installation Electrostatic Discharge ESD Handling ProcedureUnpacking Before You Begin Site PreparationEquipment and Tools Operational Considerations Configuration InformationMounting ExternalPosition the Jupiter transmitter on the side of the MLI Internal, Direct InsertionWiring Function Blocks OverviewUniversal Fieldbus Block Parameters Resource Block Jupiter Magnetostrictive Transmitter Foundation fieldbus Jupiter Magnetostrictive Transmitter Foundation fieldbus Password Parameters Transducer BlockTransducer Block Parameters Jupiter Configuration Parameters User Calibration ParametersFactory Parameters Firmware Version Analog Input BlockChannels AI Block ParametersJupiter Magnetostrictive Transmitter Foundation fieldbus Diagnostic Parameters Simulation Feature Troubleshooting TroubleshootingReference Information Status Messages Display Message Action CommentFF Segment Checklist Size Length TypeAgency specifications Atex Intrinsically safe Agency ApprovalsAgency Drawing Agency Drawing Specifications FunctionalPerformance Physical Inches mmReplacement Parts PartsModel Numbers Enhanced Jupiter Magnetostrictive TransmitterNone, defines external mount Direct Insertion Total Level Float Selection Appendix Transducer Block Parameters ReferencesJupiter Magnetostrictive Transmitter Service Policy