5.1.3 FF Segment Checklist

There can be several reasons for a FOUNDATION fieldbusinstallation to be in a faulty condition. In order to assure that communication can be established, the following requirements must be met.

Device supply voltage must be higher than 9 VDC with a maximum of 32 VDC.

Total current draw of a given segment cannot exceed the rating shown on the power conditioner and/or barrier.

Two 100 , 1 µF terminators must be connected to the network—one at each end of the segment.

Cable length plus spur length must not exceed the following values:

Number of Spurs

1 Device

2 Devices

3 Devices

4 Devices

 

 

 

 

 

25–32

 

 

 

 

 

19–24

100 ft. (30 m)

 

 

 

 

 

15–18

200 ft. (60 m)

100 ft. (30 m)

 

 

 

 

 

13–14

300 ft. (90 m)

200 ft. (60 m)

100 ft. (30 m)

 

 

 

 

 

1–12

400 ft. (120 m)

300 ft. (90 m)

200 ft. (60 m)

100 ft. (30 m)

 

 

 

 

 

Pair

Shield

Twisted

Size

Length

Type

 

 

 

 

 

 

 

Single

Yes

Yes

AWG 18

(0.8 mm2)

6,200 ft. (1,900 m)

A

 

 

 

 

 

 

 

Multi

Yes

Yes

AWG 22

(0.32 mm2)

3,900 ft. (1,200 m)

B

 

 

 

 

 

 

 

Multi

No

Yes

AWG 26

(0.13 mm2)

1,300 ft. (400 m)

C

 

 

 

 

 

 

 

Multi

Yes

No

AWG 16

(1.25 mm2)

650 ft. (200 m)

D

 

 

 

 

 

 

 

The cable shield is to be hard grounded only at one point close to the DCS. In addition, the cable shield can be capacitively grounded in multiple places to improve EMC protection.

21

46-649 Jupiter Magnetostrictive Transmitter - FOUNDATION fieldbus™

Image 24
Contents Magnetostrictive Level Transmitter Read this Manual Before Installing Table of Contents Foundation Fieldbus Overview DescriptionDevice Configuration Device Descriptions BenefitsIntrinsic Safety Installation Electrostatic Discharge ESD Handling ProcedureUnpacking Before You Begin Site PreparationEquipment and Tools Configuration Information MountingOperational Considerations ExternalPosition the Jupiter transmitter on the side of the MLI Internal, Direct InsertionWiring Function Blocks OverviewUniversal Fieldbus Block Parameters Resource Block Jupiter Magnetostrictive Transmitter Foundation fieldbus Jupiter Magnetostrictive Transmitter Foundation fieldbus Password Parameters Transducer BlockTransducer Block Parameters Jupiter Configuration Parameters User Calibration ParametersFactory Parameters Analog Input Block ChannelsFirmware Version AI Block ParametersJupiter Magnetostrictive Transmitter Foundation fieldbus Diagnostic Parameters Simulation Feature Troubleshooting TroubleshootingReference Information Status Messages Display Message Action CommentFF Segment Checklist Size Length TypeAgency specifications Atex Intrinsically safe Agency ApprovalsAgency Drawing Agency Drawing Specifications FunctionalPerformance Physical Inches mmReplacement Parts PartsModel Numbers Enhanced Jupiter Magnetostrictive TransmitterNone, defines external mount Direct Insertion Total Level Float Selection Appendix Transducer Block Parameters ReferencesJupiter Magnetostrictive Transmitter Service Policy