5.0Reference Information

5.1Troubleshooting

The Jupiter transmitter is designed and manufactured for years of trouble free operation over a wide range of condi- tions. Common transmitter problems are discussed in terms of their symptoms and recommended corrective actions.

5.1.1Troubleshooting

Problem

Solution

Transmitter does not track level (External Mount) Remove transmitter from piping column and test with re-alignment magnet. Run magnet from bottom to top of probe. Check zero and span calibration. If no change in output, consult the factory.

(Direct Insertion) Float stuck, Probe bent (Chamber)

Float inside the level gauge is moving slow or not at all.

Ensure that the magnetic level indicator is plumb.

The process fluid being measured may be too viscous and heat tracing may be required to make the material more fluid.

The specific gravity of the process fluid and float weight may need to be reverified.

The liquid being measured may contain magnetic particles collecting on the magnetic section of the float causing drag. If this happens magnetic trap assemblies can be purchased from the factory.

Visual inspection of the float may be required to see if the float has collapsed.

LEVEL value is inaccurate.

Basic configuration data is questionable. Reconfigure probe

 

length and offset. Ensure the level is accurate. Reconfigure

 

loop values.

 

 

LEVEL value fluctuates.

Turbulence, increase damping factor until readings stabilize.

 

 

19

46-649 Jupiter Magnetostrictive Transmitter - FOUNDATION fieldbus™

Image 22
Contents Magnetostrictive Level Transmitter Read this Manual Before Installing Table of Contents Foundation Fieldbus Overview DescriptionDevice Configuration Device Descriptions BenefitsIntrinsic Safety Electrostatic Discharge ESD Handling Procedure InstallationUnpacking Site Preparation Before You BeginEquipment and Tools Operational Considerations Configuration InformationMounting ExternalPosition the Jupiter transmitter on the side of the MLI Internal, Direct InsertionWiring Overview Function BlocksUniversal Fieldbus Block Parameters Resource Block Jupiter Magnetostrictive Transmitter Foundation fieldbus Jupiter Magnetostrictive Transmitter Foundation fieldbus Transducer Block Password ParametersTransducer Block Parameters User Calibration Parameters Jupiter Configuration ParametersFactory Parameters Firmware Version Analog Input BlockChannels AI Block ParametersJupiter Magnetostrictive Transmitter Foundation fieldbus Diagnostic Parameters Simulation Feature Troubleshooting TroubleshootingReference Information Status Messages Display Message Action CommentFF Segment Checklist Size Length TypeAgency specifications Atex Intrinsically safe Agency ApprovalsAgency Drawing Agency Drawing Functional SpecificationsPerformance Physical Inches mmReplacement Parts PartsModel Numbers Enhanced Jupiter Magnetostrictive TransmitterNone, defines external mount Direct Insertion Total Level Float Selection Appendix Transducer Block Parameters ReferencesJupiter Magnetostrictive Transmitter Service Policy