DCA-70USJ — OUTPUTTERMINAL PANEL CONNECTIONS
UVWO Terminal Output Voltages
Various output voltages can be obtained using the Output Terminal Lugs.. The voltages at the terminals are depen- dent on the position of the Voltage Selector Switch and the adjustment of the Voltage Regulator Control Knob.
Remember the voltage selector switch determines the range of the output voltage. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.
3Ø 240/139 Output Terminal Lug Voltages
1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 22.
Figure 22. Voltage Selector Switch 240/139V
Three-Phase Position
2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 22.
3Ø 208V/1Ø120V OutputTerminal Lug Voltages
1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 25.
Use this position for
Figure 25. Voltage Selector
Switch 3Ø-208V/1Ø-120V
Three-Phase Position
2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 26.
Figure 26. Output Terminal Lugs
3Ø-208V/120V Connections
3.Turn the voltage regulator knob (Figure 24) clockwise to increase voltage output, turn counterclockwise to decrease voltage output.
Figure 23. Output Terminal Lugs |
| To achieve a 3Ø 208V output | |
| the voltage selector switch | ||
240/139VThree Phase Connections | NOTE | ||
must be in the | |||
3. Turn the voltage regulator knob (Figure 23) clockwise to |
| position and the voltage | |
increase voltage output, turn counterclockwise to |
| regulator must be adjusted to | |
decrease voltage output. |
| 208V. |
Figure 24. Voltage Regulator Knob (139V/240V)
PAGE 30 —