Multiquip dca-70usj DCA-70USJ Generator Outputs, Voltage Selector Switch, Generator Amperage

Page 28

DCA-70USJ — GENERATOR OUTPUTS

Voltage Selector Switch

The voltage selector switch (Figure 16) is located above the output terminal panel’s Hard Wire Hook-up Panel. It has been provided for ease of voltage selection.

Generator Amperage

Table 7 describes the generator’s current output capability for both 1Ø-phase and 3Ø phase applications.

Table 7. Generator Ampere Ratings

DCA-8USJ

kW

kVA

120V

208V

240V

480V

 

 

 

 

 

 

 

Single Phase

40

N/A

166.7A x 2

N/A

166.7A

N/A

Three Phase*

56

70

N/A

155A

134A

67A

 

 

 

* Power Factor = 0.8

 

 

 

 

 

 

 

 

 

Figure 16. Voltage Selector Switch

Voltage Selector Switch Locking Button

The voltage selector switch has a locking button to protect the generator and load from being switched while the engine is running. To lock the voltage selector switch, press and hold the red button located at the bottom of the switch.

CAUTION - CHANGINGVOLTAGES

NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the open position before selecting voltage.

Generator OutputVoltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by using the voltage selector switch (Figure 15). To obtain some of the voltages as listed in Table 6 (see below) will require a fine adjustment using the voltage regulator (VR) control knob located on the control panel.

Table 6. Voltages Available

Three Phase

208V

220V

240V

416V

440V

480V

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

120V

127V

139V

240V

254V

277V

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

GFCI Receptacle Load Capability

The load capability of the GFCI receptacles is directly re- lated to the voltage being supplied at either the output termi- nals or the 3 twist lock auxilliary receptacles.

Tables 8 and 9 show what amount of current is available at the GFCI receptacles when the output terminals and twist lock receptacles are in use. Be careful that your load does not to exceed the available current capability at the recep- tacles.

Table 8. 1Ø GFCI Receptacle Load Capability

KW in Use

Available Load

Twist-Lock (CS6369)

Current (Amps)

1Ø 240/120V

GFCI Duplex NEMA

5-20R 120V

 

40

0

38.8

5 amps per receptacle

37.6

10 amps per receptacle

36.4

15 amps per receptacle

35.2

20 amps per receptacle

Table 9. 3Ø GFCI Receptacle Load Capability

KVA in Use

Available Load

(UVWO Terminals)

Current (Amps)

3Ø 240/480V

GFCI Duplex NEMA

5-20R 120V

 

70

0

65.8

5 amps per receptacle

61.7

10 amps per receptacle

57.5

15 amps per receptacle

53.4

20 amps per receptacle

PAGE 28 — DCA-70USJ — OPERATION AND PARTS MANUAL — REV. #0 (09/16/04)

Image 28
Contents Parts List NO. M2870400114 Model DCA-70USJ2 DCA-70USJ Operation and Parts Manual REV. #0 09/16/04 Heres HOW to GET Help Wilmington Ave Carson, CATable of Contents Parts Ordering Procedures When ordering parts Please supply the following informationDCA-70USJ Specifications Generator SpecificationsDCA-70USJ Dimensions TOP, Side and Front DCA85USJ Safety Message Alert Symbols You can be injured if you do not follow directionsDCA85USJ Safety Message Alert Symbols This generator, other property, orGeneral Safety DCA-70USJ Rules for Safe OperationElectrical Safety Generator GroundingBattery Safety Maintenance SafetyDCA-70USJ Rules for Safe Operation Towing &Transporting Safety EmergenciesDCA-70USJ Generator Decals Generator DecalsDCA-70USJ Generator Decals Generator Decals Cont inuedDCA-70USJ Installation Typical Generator Grounding ApplicationDCA-70USJ Installation Outdoor InstallationIndoor Installation When connecting the generatorDCA-70USJ General Information DCA-70USJ Major Components Major Components20 DCA-70USJ Operation and Parts Manual REV. #0 09/16/04 Ammeter phase-selector switch Be switched offAdjustment of the generator’s output voltage OnlyDCA-70USJ Engine Operating Panel DCA-70USJ Engine Operating Panel DCA-70USJ Output Terminal Panel Familiarization Output Terminal Familiarization120VAC Gfci Receptacles F.C.I. ReceptacleConnecting Loads Blower FanSingle Phase Load Three Phase LoadDCA-70USJ Load Application Motors and motor-drivenVoltage Selector Switch DCA-70USJ Generator OutputsGenerator Amperage Generator OutputVoltagesDCA-70USJ Gauge Reading How to Read the OutputTerminal GaugesReading Amperage Three-Phase Position DCA-70USJ Outputterminal Panel ConnectionsUvwo Terminal Output Voltages 3Ø 240/139 Output Terminal Lug Voltages3Ø 480/277 Output Terminal Lug Voltages 1Ø 240V/120V Output Terminal Lug VoltagesDCA-70USJ PRE-SETUP Circuit BreakersLubrication Oil Fuel CheckRefueling Procedure RefuelingCleaning the Radiator Air Cleaner Fan BeltTensionOperation FreezingWeather Vol % Freezing PointBattery Battery Cable InstallationWiring AlternatorBefore Starting Engines exhaust contains harmful emissionsDirect exhaust away from nearby personnel Close all engine enclosure doors FigureStarting Manual Position to start the engine FigureOil Pressure Gauge Starting Auto Mode Place the Mpec Control Switch in the Auto positionShutdown Procedure DCA-70USJ Generator SHUT-DOWN ProcedureEmergency Shutdown Procedure DCA-70USJ Maintenance Air Removal Check Oil LevelReplacing Oil Filter Replacing Fuel FilterDCA-70USJ Maintenance To ensure adequate startingDCA-70USJ -TRAILER Maintenance Trailer MaintenanceDCA-70USJ -TRAILER Maintenance Brake AdjustmentBrakes Check the wheel and drum for free rotationTireWear/Inflation Tires/Wheels/Lug NutsSuspension Lug NutTorque Requirements Start all wheel lug nuts by handDCA-70USJ -TRAILERWIRING Diagram Trailer/Towing Vehicle Wiring DiagramDCA-70USJ Generatorwiring Diagram DCA-70USJ Enginewiring Diagram Engine Wiring DiagramDCA-70USJ -TROUBLESHOOTING Generator DCA-70USJ -TROUBLESHOOTING Engine Controller Engine Controller Troubleshooting MpecDCA-70USJ Operation and Parts Manual REV. #0 09/16/04 Items Found In the Items Number Column Explanation of Code in Remarks ColumnIf more than one of the same Part number on this Suggested Spare Parts list DCA-70USJ Suggested Spare PartsDCA-70USJ Generator Assy B5110100602 81010700330012810035 8101611004DCA-70USJ Control BOX Assy M2213000702 03300001800601808824 002100508060 DCA-70USJ Operation and Parts Manual REV. #0 09/16/04 DCA-70USJ Control BOX Assy DCA-70USJ Engine & Radiator Assy M2923200014 0602041292RE504836 060204259564 DCA-70USJ Operation and Parts Manual REV. #0 09/16/04 0602022561 06033065900603300285 0605511395DCA-70USJ Outputterminal Assy M2230700113 M2233000004M2233100004 0039312000DCA-70USJ Battery Assy 0602220187 627MFDM9310500014 M9103000304DCA-70USJ Muffler Assy M2330100803 0017112030M2333000703 M2333200204DCA-70USJ Fueltank Assy M2363000902 06055050700605501073 0605516090DCA-70USJ Enclosure #1 Assy M2413001502 M23633002030603306797 M242300091276 DCA-70USJ Operation and Parts Manual REV. #0 09/16/04 0010120050 28A 003002000028B 0040020000 28C 0041220000DCA-70USJ Enclosure #2 Assy Enclosure #2 AssyM3443000812 M3493303203M3443000914 M3493303304DCA-70USJ Enclosure #3 Assy 0229200870 02292011300229201240 0228900660DCA-70USJ Name Plate Assy M1550000204 M1550000703M2550000304 M2550000603Terms and Conditions of Sale Parts FreightpolicyDCA-70USJ Operation and Parts Manual REV. #0 09/16/04 Your Local Dealer is