DCA-25SSIU2 (60 HZ)— GAUGE READING

How to Read the OutputTerminal Gauges.

The gauges and selector switches on the control panel DO NOT effect the generator output. They are provided to help observe how much power is being supplied at the Output terminals lugs.

Before taking a reading off either gauge, set the Voltage Selector Switch (Figure 17) to the position which produces the required voltage (For example, for 3Ø 240V,

choose the center 3Ø 240/ 139V position on the volt- age selector switch.)

Reading Amperage

To determine the amperage at a terminal lug, set the AC Ammeter Change-Over Switch to the appropriate setting (Figure 20) to activate the AC Ammeter Gauge (Figure 21) and read the available amperage at the terminal lug.

For example, to measure the amperage at the U terminal lug, set the AC Ammeter Change-Over Switch to U and read the AC Ammeter Gauge.

Figure 17. Voltage

Selector Switch 240/

139VThree Phase

Position

NOTE

Reading Voltage

For 3Ø 208V/1Ø,120V, place the Voltage Selector Switch in the 3 Phase 240/139 position.

Figure 20. AC Ammeter

Change-Over Switch

NOTE

Figure 21. AC Ammeter (Amp reading on U lug)

The ammeter gauge will only show a reading when the Output Terminal Lugs are connected to a load and in use.

To determine the voltage between two terminal lugs, set the AC Voltmeter Change-Over Switch to the appropriate setting (Figure 18) to activate the AC Voltmeter Gauge (Figure 19) and read the available voltage between the two lugs.

For example, to measure the voltage between the W and U terminal lugs, set the AC Voltmeter Change-Over Switch to W-U and read the AC Voltmeter Gauge.

Figure 18. AC Voltmeter Figure 19. AC Voltmeter Gauge Change-Over Switch

DCA-25SSIU2 (60 HZ)— OPERATION AND PARTS MANUAL — REV. #0 (01/27/06) — PAGE 27

Image 27
Contents Model DCA-25SSIU2 Parts List NO. M1870300804Page Wilmington Ave Carson, CA Heres HOW to GET HelpTable of Contents When ordering parts Please supply the following information Parts Ordering ProceduresDCA-25SSIU2 60 HZ- Specifications Dimensions DCA-25SSIU2 60 HZ- Dimensions TOP, Side and FrontHas been developed to provide DCA-25SSIU2 60 HZ Safety Message Alert SymbolsThis generator, other property, or DCA-25SSIU2 60 HZ Safety Message Alert SymbolsGeneral Safety DCA-25SSIU2 60 HZ- Rules for Safe OperationBurns Electrical Safety DCA-25SSIU2 60 HZ- Rules for Safe OperationGenerator Grounding Battery Safety Maintenance SafetyEmergencies Towing &Transporting SafetyGenerator Decals DCA-25SSIU2 60 HZ- Generator DecalsDCA-25SSIU2 60 HZ- Generator Decals DCA-25SSIU2 60 HZ- Installation When connecting the generator DCA-25SSIU2 60 HZ- InstallationOutdoor Installation Indoor InstallationDCA-25SSIU2 60 HZ- General Information Generator Major Components DCA-25SSIU2 60 HZ- Major ComponentsDCA-25SSIU2 60 HZ- Generator Control Panel DCA-25SSIU2 60 HZ- Engine Operating Panel Output Terminal Familiarization DCA-25SSIU2 60 HZ- Output Terminal Panel FamiliarizationF.C.I. Receptacle 120VAC Gfci Receptacles DCA-25SSIU2 60 HZ- Output Terminal Panel FamiliarizationBlower Fan Connecting LoadsMotors and motor-driven Single Phase LoadThree Phase Load DCA-25SSIU2 60 HZ- Load ApplicationGenerator Amperage Voltage Selector SwitchDCA-25SSIU2 60 HZ- Generator Outputs Generator OutputVoltagesHow to Read the OutputTerminal Gauges DCA-25SSIU2 60 HZ- Gauge ReadingReading Amperage 3Ø-240/139 Output Terminal Lug Voltages Three-Phase PositionDCA-25SSIU2 60 HZ- Output Terminal Panel Connections Uvwo Terminal Output VoltagesDCA-25SSIU2 60 HZ- Output Terminal Panel Connections 3Ø 480/277 Output Terminal Lug Voltages1Ø 240V/120V Output Terminal Lug Voltages Fuel Check DCA-25SSIU2 60 HZ- PRE-SETUPCircuit Breakers Lubrication OilDCA-25SSIU2 60 HZ- PRE-SETUP Refueling ProcedureRefueling Vol % Freezing Point Cleaning the RadiatorAir Cleaner Fan Belt Tension Operation FreezingWeatherWiring BatteryBattery Cable Installation When connecting battery do the followingDirect exhaust away from nearby personnel DCA-25SSIU2 60 HZ- Generator START-UP ProcedureBefore Starting Engines exhaust contains harmful emissionsFrequency Meter Hz DCA-25SSIU2 60 HZ- GEN. START-UP PROCEDURE/SHUTDOWN Turn the ignition switch key to the Stop positionRemove all loads from the generator DCA-25SSIU2 60 HZ- Maintenance Replacing Oil Filter Cleaning the Fuel StrainerAir Removal Check Oil LevelTo ensure adequate starting DCA-25SSIU2 60 HZ- MaintenanceTrailer Maintenance DCA-25SSIU2 60 HZ-TRAILER MaintenanceCheck the wheel and drum for free rotation DCA-25SSIU2 60 HZ-TRAILER MaintenanceBrake Adjustment BrakesTires/Wheels/Lug Nuts Tire Wear/InflationSuspension DCA-25SSIU2 60 HZ-TRAILER Maintenance Lug Nut Torque RequirementsStart all wheel lug nuts by hand DCA-25SSIU2 60 HZ-TRAILERWIRING Diagram Generator Wiring Diagram DCA-25SSIU2 60 HZ- Generatorwiring DiagramDCA-25SSIU2 60 HZ- Enginewiring Diagram Generator Troubleshooting DCA-25SSIU2 60 HZ-TROUBLESHOOTING GeneratorDCA-25SSIU2 60 HZ-TROUBLESHOOTING Engine Engine does not startStarter does not run DCA-25SSIU2 60 HZ-TROUBLESHOOTING Engine Explanation of Code in Remarks Column Items Found In the Items Number ColumnIf more than one of the same DCA-25SSIU2 60 HZ- Suggested Spare Parts Part number on this Suggested Spare Parts listDCA-25SSIU2 60 HZ- Generator Assy 8001070003 B11102006027961025004 0601822630DCA-25SSIU2 60 HZ- Control BOX Assy 0601842384 M12130009020601870430 0021004075Control BOX ASSY.CONT 0601840073 0601808985 AC AMMETER, ACF-6 0~50A/100A5A 06018010400601806859 0601801041DCA-25SSIU2 60 HZ- Engine Operating Panel Assy 2A# 0601810245 BULB, E-10 T-10 DC18V 0602120095 89704441808944024980 0602103092DCA-25SSIU2 60 HZ- Engine & Radiator Assy M1305200204 M19232000440602041210 M1305200304DCA-25SSIU2 60 HZ- Engine & Radiator ASSY. 0605511395 VALVE, XV500P-8 0603306395 Hose Joint 0602021070 06020225610603306590 0603300285Output Terminal Assy DCA-25SSIU2 60 HZ- Outputterminal Assy0039308000 M1230700003M9220000004 M9220000104DCA-25SSIU2 60 HZ- Battery Assy 0602220920 0602220185M9310500014 M9103000304DCA-25SSIU2 60 HZ- Muffler Assy M1333200014 0602300390M1333201703 8970420280DCA-25SSIU2 60 HZ- Fuel Tank Assy DCA-25SSIU2 60 HZ- Fueltank Assy Enclosure Assy DCA-25SSIU2 60 HZ- Enclosure AssyM1493104903 M1413002802M1413400004 M1423001802Enclosure ASSY.CONT DCA-25SSIU2 60 HZ- Enclosure ASSY.M1453003903 0016908055M1453003803 33A M1493405604DCA-25SSIU2 60 HZ- Rubber Seals Assy M1490300004 02289011700228900695 0228900725DCA-25SSIU2 60 HZ- Nameplate and Decals M1550017003 M1550000104M1550000204 M1550001603Freightpolicy Terms and Conditions of Sale PartsPage Your Local Dealer is
Related manuals
Manual 82 pages 62.92 Kb

DCA-25SSIU2 specifications

The Multiquip DCA-25SSIU2 is a versatile and powerful diesel generator, designed to meet the needs of various industries while providing a reliable source of power. This model is particularly popular in construction, event management, and emergency backup supply applications. With its robust build and advanced features, the DCA-25SSIU2 stands out as a top choice for professionals seeking durability and efficiency.

One of the significant features of the DCA-25SSIU2 is its impressive power output. The generator delivers a continuous output of 25 kVA, making it suitable for powering heavy machinery, tools, and equipment. This model is equipped with a turbocharged, liquid-cooled YANMAR engine, known for its performance and fuel efficiency. The engine operates quietly, ensuring minimal noise pollution in sensitive environments.

Built to withstand harsh conditions, the DCA-25SSIU2 is housed in a sturdy steel frame enclosure. The design not only protects the generator from the elements but also reduces noise levels. The enclosure features a weather-resistant finish, making it ideal for both indoor and outdoor applications. Additionally, the unit's compact size allows for easy transportation and storage, which is an essential consideration for contractors on the go.

The DCA-25SSIU2 incorporates advanced technology to enhance performance and user experience. It features a digital control panel, offering intuitive monitoring of generator status, fuel consumption, and operational hours. Automatic voltage regulation ensures a stable output, protecting connected devices from voltage fluctuations.

Fuel efficiency is another highlight of this generator. The DCA-25SSIU2 operates on diesel, which is not only readily available but also provides a longer run time compared to gasoline generators. The large fuel tank capacity allows for extended periods of operation without frequent refueling.

Safety is a critical aspect of the DCA-25SSIU2. The generator is equipped with safety features such as low oil shut-off, overload protection, and a heavy-duty frame for stability. These elements ensure that the generator operates safely and reliably, even in demanding situations.

In conclusion, the Multiquip DCA-25SSIU2 diesel generator combines power, efficiency, and ruggedness. Its blend of advanced features, fuel efficiency, and safety make it an excellent choice for a wide range of applications. Whether for construction projects, outdoor events, or emergency power needs, the DCA-25SSIU2 stands as a testament to Multiquip's commitment to quality and innovation in the generator market.