DCA-25SSIU2 (60 HZ)— GENERAL INFORMATION
DCA-25SSIU2 (60 Hz) Series Familiarization
Generator
The MQ Power Model
Engine Operating Panel
The “Engine Operating Panel” is provided with the following:
■Tachometer
■Water Temperature Gauge
■Water Temperature Alarm Lamp
■Oil Pressure Gauge
■Oil Pressure Alarm Lamp
■Charging Ammeter Gauge
■Fuel Level Gauge
■
■Panel Light/Panel Light Switch
■Ignition Switch
■Fuel Filter Water Level Alarm Lamp
Generator Control Panel
The “Generator Control Panel” is provided with the following:
■Frequency Meter (Hz)
■AC Ammeter (Amps)
■AC Voltmeter (Volts)
■Ammeter
■Voltmeter
■Voltage Regulator
■
■“Control Box” (located behind the Gen. Control Panel)
■Automatic Voltage Regulator
■Current Transformer
■
■Voltage Rectifier
■Starter Relay
■Voltage Selector Switch
Output Terminal Panel
The “Output Terminal Panel” is provided with the following:
■Two 120/240V output receptacles
■Two auxiliary circuit breakers, 50A
■Two 120V output receptacles (GFCI), 20A
■Two GFCI circuit breakers, 20A
■Five output terminal lugs (3Ø power)
■Battery Charger (Optional)
■Water Heater (Optional)
Open Delta Excitation System
The
There are four connections of the open delta A, B, C and D. During steady state loads, the power from the voltage regulator is supplied from the parallel connections of A to B, A to D, and C to D. These three phases of the voltage input to the voltage regulator are then rectified and are the excitation current for the exciter section.
When a heavy load, such as a motor starting or a short circuit occurs, the automatic voltage regulator (AVR) switches the configuration of the open delta to the series connection of B to C.This has the effect of adding the voltages of each phase to provide higher excitation to the exciter section and thus better voltage response during the application of heavy loads.
The connections of the AVR to the AC output windings are for sensing only. No power is required from these windings.
The
PAGE 18 —