2. Electrical
In a domestic installation, the rating of the electricity supplier’s fuse and the consumer unit must be adequate for the additional demand. All Mira electric showers are high power units, it is essential to contact your electricity supplier to ensure that the supply is adequate for the product. Voltage drop due to local heavy demand will reduce the shower’s performance.
The appliance must be earthed by connecting the
Supplementary bonding: Within the bathroom or shower room, all
accessible conductive parts of electrical equipment and extraneous
conductive parts (metal parts) that are likely to introduce earth potential, must be electrically bonded to earth using a minimum cable size of 4.0mm2 if the cable is not mechanically protected, (2.5 mm2 if mechanically protected).
The minimum cable size
As a guide only, and in accordance with BS 7671 we recommend close circuit protection: i.e. 9.8 kW = 45 Amp
It is strongly recommended that a 30 mA Residual Current Device (RCD) is included in the electrical circuit. This may be part of the consumer unit or a separate unit.
A separate, permanently connected supply must be taken from the consumer unit to the appliance through a
DO NOT twist the individual cable cores of either the live or neutral conductors, as this will prevent them from entering the terminal block.
DO NOT exert strain on the terminal block. Ensure that the electrical
connections are tightly screwed down.