1.13 ENGINE OIL RECOMMENDATIONS

Section 2 — Installation

Guardian Liquid-cooled 25 kW Generator

1.13 ENGINE OIL RECOMMENDATIONS

The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE, SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:

 

Temperature

Oil Grade (Recommended)

 

 

Above 80° F (27° C)

SAE 30W or 15W-40

 

 

32° to 80° F (-1° to 27° C)

SAE 20W-20 or 15W-40

 

 

Below 32° F (0° C)

SAE 10W or 15W-40

 

 

 

 

 

 

 

 

 

Any attempt to crank or start the engine

!before it has been properly serviced with the recommended oil may result in an engine fail- ure.

1.14 COOLANT RECOMMENDATIONS

Use a mixture of half low silicate ethylene glycol base anti-freeze and half deionized water. Cooling system capacity is about 8 U.S. quarts (7.6 liters). Use only deionized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the rec- ommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.

Do not use any chromate base rust inhibitor

!with ethylene glycol base anti-freeze or chromiumhydroxide (“green slime”) forms and will cause overheating. Engines that have been operated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or addi- tives will also cause overheating. DO NOT use any soluble oil inhibitor for this equipment.

1.15 BEFORE INSTALLATION

Before installing this equipment, check the ratings of both the generator and the transfer switch. Read “Emergency Isolation Method” and “Total Circuit Isolation Method” in Sections 2.5 and 2.6.

The generator’s rated wattage/amperage capacity must be adequate to handle all electrical loads that the unit will power. It may be necessary to group the critical (essential) loads together and wire them into a separate “emergency” distribution panel.

This generator can be installed in conjunction with an engineered Generac “GTS” type transfer switch, if necessary.

The standard prepackaged transfer switch does not have sensing or controlling circuit boards. Instead, the generator control console houses a “Printed Circuit Board Assembly”, which controls all phases of operation, including engine start up and load transfer.

2.1STANDBY GENERATOR INSTALLATION

TemperatureAny attempt to crank or start the engine DANGER

Connecting this generator to an electrical sys- tem normally supplied by an electric utility shall be by means of a transfer switch, so as to isolate the electric system from the utility distribution system when the generator is operating. Failure to isolate the electric sys- tem by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.

If an open bottom is used, the engine-genera- tor must be installed over non-combustible materials and should be located such that com- bustible materials are not capable of accumu- lating under the generator set.

Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regulations should install this standby electric power system. The installation must comply strictly with all codes, standards and regula- tions pertaining to the installation.

After the system has been installed, do nothing

!that might render the installation in noncompli- ance with such codes, standards and regula- tions.

NOTE:

For more information about the installation of a standby system contact a Generac Authorized Service Dealer.

‹2.1.1 NFPA STANDARDS

The following published standards booklets pertain- ing to standby electric systems are available form the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269:

NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES.

NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-

TEMS FOR HEALTH CARE FACILITIES.

NFPA No. 220, STANDARD TYPES OF BUILDING CONSTRUCTION

8 Generac® Power Systems, Inc.

Image 10
Contents Liquid-cooled, Prepackaged Standby Generators SHOULD ATTEMPT INSTALLATIONOwner’s Manual This manual should remain with the unit‹ HOW TO OBTAIN SERVICE AUTHORIZED SERVICE DEALER LOCATION‹ OPERATION AND MAINTENANCE INTRODUCTIONTable of Contents Guardian Liquid-cooled 25 kW GeneratorParts of the generator are rotating and/or hot GENERAL HAZARDSDespite the safe design of this generator during operation. Exercise care near running gen- eratorsEXPLOSION HAZARDS ELECTRICAL HAZARDSFIRE HAZARDS ‹ STANDARDS INDEX1.3 AUTOMATIC SYSTEM OPERATION 1.2 TRANSFER SWITCH1.1 GENERATOR 1.4 GENERATOR AC CONNECTION SYSTEMS‹ 1.7.3 LOW COOLANT LEVEL SWITCH ‹ 1.7.1 LOW OIL PRESSURE SWITCH‹ 1.7.2 HIGH COOLANT TEMPERATURE SWITCH Figure 1.4 - Low Oil Pressure Switch‹ 1.8.1 UNPACKING PRECAUTIONS 1.10 SPECIFICATIONS‹ 1.7.6 LOW BATTERY 1.8 UNPACKING1.11 FUEL CONSUMPTION 1.12 RECONFIGURING THE FUEL SYSTEM FOR LP VAPORFigure 1.8 - Reconfigure the Fuel System ‹ 1.10.2 GENERATOR1.13 ENGINE OIL RECOMMENDATIONS 1.15 BEFORE INSTALLATION2.1 STANDBY GENERATOR INSTALLATION 1.14 COOLANT RECOMMENDATIONS2.2 GENERATOR LOCATION 2.3 GENERATOR MOUNTING AND SUPPORT2.4 BASIC STANDBY ELECTRIC SYSTEM ‹ 2.1.2 OTHER PUBLISHED STANDARDS2.6 TOTAL CIRCUIT ISOLATION METHOD 2.9 USING AN ENGINEERED “GTS” TRANSFER SWITCH2.5 EMERGENCY CIRCUIT ISOLATION METHOD 2.7 GROUNDING THE GENERATOR‹ 2.10.1 VENTED BATTERIES 2.10 BATTERY INSTALLATIONPos2 OFF - Standard Prepackaged ATS Application Standby generators installed with automatic2.11 PREPARATION BEFORE START-UP 3.1 ENGINEERED GTS TRANSFER SWITCH‹ 2.11.2 TRANSFER SWITCH ‹ 2.11.1 PRIOR TO INITIAL START-UP‹ 3.2.5 SET EXERCISE TIME SWITCH ‹ 3.2.2 FAULT INDICATOR LEDS‹ 3.2.1 AUTO/OFF/MANUAL SWITCH 3.2 CONTROL CONSOLE COMPONENTS3.3 MANUAL TRANSFER AND START-UP 3.4 ENGINE GOVERNOR ADJUSTMENTS‹ 3.2.6 SYSTEM READY LED 3.6 AUTOMATIC OPERATION Figure 3.2 - Engine Governor AdjustmentFigure 3.3 - “Set Exercise Time” Switch 3.7 WEEKLY EXERCISE CYCLEA. EVERY THREE MONTHS 3.8 CONTROL BOARD DIP SWITCH SETTINGS4.1 MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES B. ONCE EVERY SIX MONTHS4.4 CYLINDER HEAD PROCEDURE 4.2 EXHAUST MANIFOLD PROCEDURE4.3 INTAKE MANIFOLD PROCEDURE Figure 4.1 - Intake Manifold Installation4.6 OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM 4.8 MAINTENANCE OWNER/ OPERATOR CAN PERFORM4.7 CHECKING FLUID LEVELS ‹ 4.8.8 CHECK FAN BELT ‹ 4.8.11 CHANGING THE ENGINE AIR CLEANERFigure 4.4 - Setting the Spark Plug Gap ‹ 4.8.9 INSPECT ENGINE GOVERNOR‹ 4.9.2 BATTERY 4.9 MISCELLANEOUS MAINTENANCE‹ 4.9.1 CLEANING THE GENERATOR ‹ 4.9.3 BATTERY MAINTENANCETurn off the battery charger turn OFF utility supply to ATS 4.10 SCHEDULED MAINTENANCEService Maintenance Interval Information Remove the negative battery cableLevel MaintenanceTasks Maintenance CAUSE TROUBLESHOOTING POINTSPROBLEM CORRECTIONGenerac Power Systems, Inc 26 Generac Power Systems, Inc Wiring Diagram - 2.5L Engine 15kW & 20kW units -Drawing No. 0F1411Section 7 - Electrical Data Generac Power Systems, Inc 28 Generac Power Systems, Inc Generac Power Systems, Inc Wiring Diagram - 2.5L Engine 25kW unit -Drawing No. 0E9982-B 30 Generac Power Systems, IncGenerac Power Systems, Inc Electrical Schematic - 2.5L 25kW unit - Drawing No. 0E9983-B 32 Generac Power Systems, IncGenerac Power Systems, Inc MOUNT HARNESS WIRE34 Generac Power Systems, Inc BLOCK ENGINEDESCRIPTION COVER CABLE PANEL FOR ACCESSGROUND WIRE FASTENER TO SECUREEnclosure - Drawing No. 0E9720-D 38 Generac Power Systems, Inc HINGE CONTINUOUS 1.5L CTRL PNL 40 Generac Power Systems, Inc DESCRIPTION STEPPER MOTOR UNITS ONLY 42 Generac Power Systems, IncGuardian Liquid-cooled 25 kW Generator Engine - Drawing No. 0E9918-E TO RADIATORSERPENTINE BELT - 41 3/8 LENGTH SOURCE GENERAC-BOSCH GOVGASKET, 2.5L FORD EXHAUST MAN BRKT,D.C. ALTERNATORMACHINEDCOVER 0E1028A I/NTO ENGINE 44 Generac Power Systems, IncGuardian Liquid-cooled 25 kW Generator 46 Generac Power Systems, Inc LOCKTIGHTLEADS Alternator - Drawing No. 0E8660-CSTR 390 35AD1 HSB 382MM LONG3.0L FORD & 2.5L FORD ROTOR REPLACEMENT PARTSROTOR 390 30KW 1P DIRECT HSB 3.0L FORD & 2.5L FORD CONDUIT FLEX 1-1/4 30 LG - 3.0L FORD & 3.9L CHRYSLER48 Generac Power Systems, Inc SCREW HHC M8-1.25 X 60 G8.8 FTCOATING SECURE WIRE HARNESSITEM 13 NEOPRENE WITH TIE WRAP AS SHOWNSUPPORT,RADIATOR 2.5L FORD 50 Generac Power Systems, Inc1024 HOSE, UPPER RADIATOR 174MMSection 9 - Installation Diagram Installation Diagram - Drawing No. 0F1020-APURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES YOUR WARRANTY RIGHTS AND OBLIGATIONSMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE CALIFORNIA EMISSION CONTROL WARRANTY STATEMENTEMISSION CONTROL SYSTEM WARRANTY EMISSION RELATED PARTS INCLUDE THE FOLLOWINGTHIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING GENERAC POWER SYSTEMS TWO YEAR LIMITED WARRANTY FOR GUARDIANWARRANTY SCHEDULE GENERAC POWER SYSTEMS, INC P.O. BOX 297 WHITEWATER, WI