Generac Power Systems 005040-0, 005053-1, 005054-0 Automatic Operation, Weekly Exercise Cycle

Page 17
Figure 3.2 — Engine Governor Adjustment

Section 3 - Operation

Guardian Liquid-cooled 25 kW Generator

3.Under no load condition, increase the GAIN pot as much as possible without causing instability.

4.Apply 1/4, 1/2, 3/4 and full load to the unit. Decrease the GAIN pot if there is instability at any load point.

5.Under full load condition, increase the stability pot until the unit returns to 60 Hertz (or 50 Hertz in 50 Hertz applications).

6.Reduce load to 3/4, 1/2, 1/4 and no load. Decrease the stability pot if there is instability at any load point.

7.Adjust differential pot to make the recovery to load changes even faster and minimize load change undershoot and overshoot. If it is set too high, it may introduce oscillations at some load. It can be set to zero (full CCW) if a small amount causes oscillations at some load.

Figure 3.2 — Engine Governor Adjustment

Let the generator engine run at no-load for a few minutes, to stabilize internal unit temperatures.

On the generator console, set the Auto/Off/ Manual switch to Off. Wait for engine to come to a complete stop.

For transfer to utility position, refer to the Owner’s Manual of the particular transfer switch.

Turn on the utility power supply to the transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads.

3.6AUTOMATIC OPERATION

To set the system for fully automatic operation, pro- ceed as follows:

Check that load circuits are connected to the utility power supply.

Set the AUTO/OFF/MANUAL switch to its AUTO position.

Set the generator main circuit breaker to its ON or CLOSED position.

3.7WEEKLY EXERCISE CYCLE

The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load to the generator output and continue to run until util- ity returns.

On the day, and at the time of day chosen for the gen- erator to exercise, set the weekly exercise cycle as fol- lows:

1.Place the AUTO/OFF/MANUAL switch in the auto position (Figure 3.3).

2.Press and hold the “Set Exercise” switch for five seconds, then release.

Figure 3.3 - “Set Exercise Time” Switch

3.5RETRANSFER AND SHUTDOWN

When utility power source voltage has been restored, electrical loads may be transferred back to that source and the generator can be shut down as fol- lows:

• Verify that utility power supply voltage to the trans-

fer switch has been positively turned Off, using

whatever means provided (such as utility main line

AUTO

OFF

MANUAL

SYSTEM READY

LOW BATTERY

3.6AUTOMATIC OPERATION3.7WEEKLY EXERCISE CYCLE LOW OIL PRESSURE LOW COOLANT LEVEL

HI COOLANT TEMPERATURE Figure 3.3 - “Set Exercise Time” Switch3.5RETRANSFER AND SHUTDOWN OVER SPEED

OVER CRANK

LED INDICATORS:

0F0653

OFF

ON

SET

EXERCISE

TIME

TO SET EXERCISER TIME

1)PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.

2)HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR

THREE SECONDS AND RELEASE. THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR

10 SECONDS. THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.

RISK OF ELECTRICAL PARTS INSIDE. R

FOR STAND-BY SERV TRANSFER SWITCH IN

ATTENTION: POUR L' ICE A UN COM CAN

NAUTOMATICA INJURY REMO

circuit breaker).

• Set the generator’s main circuit breaker to its Off

or Open position.

FLASHING GREEN LED = NO UTILITY SENSE

5 FLASHING RED LED'S = EXERCISER NOT SET

(IN AUTO MODE ONLY) SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON RED LED'S = INDIVIDUAL FAULT

(SEE OWNER'S MANUAL FOR COMPLETE DETAILS)

THIS EMERGE

Generac® Power Systems, Inc. 15

Image 17
Contents Owner’s Manual SHOULD ATTEMPT INSTALLATIONLiquid-cooled, Prepackaged Standby Generators This manual should remain with the unit‹ OPERATION AND MAINTENANCE AUTHORIZED SERVICE DEALER LOCATION‹ HOW TO OBTAIN SERVICE INTRODUCTIONGuardian Liquid-cooled 25 kW Generator Table of ContentsDespite the safe design of this generator GENERAL HAZARDSParts of the generator are rotating and/or hot during operation. Exercise care near running gen- eratorsFIRE HAZARDS ELECTRICAL HAZARDSEXPLOSION HAZARDS ‹ STANDARDS INDEX1.1 GENERATOR 1.2 TRANSFER SWITCH1.3 AUTOMATIC SYSTEM OPERATION 1.4 GENERATOR AC CONNECTION SYSTEMS‹ 1.7.2 HIGH COOLANT TEMPERATURE SWITCH ‹ 1.7.1 LOW OIL PRESSURE SWITCH‹ 1.7.3 LOW COOLANT LEVEL SWITCH Figure 1.4 - Low Oil Pressure Switch‹ 1.7.6 LOW BATTERY 1.10 SPECIFICATIONS‹ 1.8.1 UNPACKING PRECAUTIONS 1.8 UNPACKINGFigure 1.8 - Reconfigure the Fuel System 1.12 RECONFIGURING THE FUEL SYSTEM FOR LP VAPOR1.11 FUEL CONSUMPTION ‹ 1.10.2 GENERATOR2.1 STANDBY GENERATOR INSTALLATION 1.15 BEFORE INSTALLATION1.13 ENGINE OIL RECOMMENDATIONS 1.14 COOLANT RECOMMENDATIONS2.4 BASIC STANDBY ELECTRIC SYSTEM 2.3 GENERATOR MOUNTING AND SUPPORT2.2 GENERATOR LOCATION ‹ 2.1.2 OTHER PUBLISHED STANDARDS2.5 EMERGENCY CIRCUIT ISOLATION METHOD 2.9 USING AN ENGINEERED “GTS” TRANSFER SWITCH2.6 TOTAL CIRCUIT ISOLATION METHOD 2.7 GROUNDING THE GENERATORPos2 OFF - Standard Prepackaged ATS Application 2.10 BATTERY INSTALLATION‹ 2.10.1 VENTED BATTERIES Standby generators installed with automatic‹ 2.11.2 TRANSFER SWITCH 3.1 ENGINEERED GTS TRANSFER SWITCH2.11 PREPARATION BEFORE START-UP ‹ 2.11.1 PRIOR TO INITIAL START-UP‹ 3.2.1 AUTO/OFF/MANUAL SWITCH ‹ 3.2.2 FAULT INDICATOR LEDS‹ 3.2.5 SET EXERCISE TIME SWITCH 3.2 CONTROL CONSOLE COMPONENTS‹ 3.2.6 SYSTEM READY LED 3.4 ENGINE GOVERNOR ADJUSTMENTS3.3 MANUAL TRANSFER AND START-UP Figure 3.3 - “Set Exercise Time” Switch Figure 3.2 - Engine Governor Adjustment3.6 AUTOMATIC OPERATION 3.7 WEEKLY EXERCISE CYCLE4.1 MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES 3.8 CONTROL BOARD DIP SWITCH SETTINGSA. EVERY THREE MONTHS B. ONCE EVERY SIX MONTHS4.3 INTAKE MANIFOLD PROCEDURE 4.2 EXHAUST MANIFOLD PROCEDURE4.4 CYLINDER HEAD PROCEDURE Figure 4.1 - Intake Manifold Installation4.7 CHECKING FLUID LEVELS 4.8 MAINTENANCE OWNER/ OPERATOR CAN PERFORM4.6 OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM Figure 4.4 - Setting the Spark Plug Gap ‹ 4.8.11 CHANGING THE ENGINE AIR CLEANER‹ 4.8.8 CHECK FAN BELT ‹ 4.8.9 INSPECT ENGINE GOVERNOR‹ 4.9.1 CLEANING THE GENERATOR 4.9 MISCELLANEOUS MAINTENANCE‹ 4.9.2 BATTERY ‹ 4.9.3 BATTERY MAINTENANCEService Maintenance Interval Information 4.10 SCHEDULED MAINTENANCETurn off the battery charger turn OFF utility supply to ATS Remove the negative battery cableTasks MaintenanceLevel Maintenance PROBLEM TROUBLESHOOTING POINTSCAUSE CORRECTIONGuardian Liquid-cooled 25 kW Generator Section 7 - Electrical Data Wiring Diagram - 2.5L Engine 15kW & 20kW units -Drawing No. 0F141126 Generac Power Systems, Inc Section 7 - Electrical Data 28 Generac Power Systems, Inc Section 7 - Electrical Data 30 Generac Power Systems, Inc Wiring Diagram - 2.5L Engine 25kW unit -Drawing No. 0E9982-BSection 7 - Electrical Data 32 Generac Power Systems, Inc Electrical Schematic - 2.5L 25kW unit - Drawing No. 0E9983-BSection 7 - Electrical Data 34 Generac Power Systems, Inc HARNESS WIREMOUNT BLOCK ENGINEDESCRIPTION GROUND WIRE PANEL FOR ACCESSCOVER CABLE FASTENER TO SECUREEnclosure - Drawing No. 0E9720-D 38 Generac Power Systems, Inc HINGE CONTINUOUS 1.5L CTRL PNL 40 Generac Power Systems, Inc Section 8 - Exploded Views and Parts Guardian Liquid-cooled 25 kW Generator Engine - Drawing No. 0E9918-E 42 Generac Power Systems, IncSTEPPER MOTOR UNITS ONLY TO RADIATORGASKET, 2.5L FORD EXHAUST MAN SOURCE GENERAC-BOSCH GOVSERPENTINE BELT - 41 3/8 LENGTH BRKT,D.C. ALTERNATORMACHINEDTO ENGINE 0E1028A I/NCOVER 44 Generac Power Systems, IncSection 8 - Exploded Views and Parts LEADS LOCKTIGHT46 Generac Power Systems, Inc Alternator - Drawing No. 0E8660-CROTOR 390 30KW 1P DIRECT HSB 3.0L FORD & 2.5L FORD ROTOR REPLACEMENT PARTSSTR 390 35AD1 HSB 382MM LONG3.0L FORD & 2.5L FORD CONDUIT FLEX 1-1/4 30 LG - 3.0L FORD & 3.9L CHRYSLERSCREW HHC M8-1.25 X 60 G8.8 FT 48 Generac Power Systems, IncITEM 13 NEOPRENE SECURE WIRE HARNESSCOATING WITH TIE WRAP AS SHOWN1024 50 Generac Power Systems, IncSUPPORT,RADIATOR 2.5L FORD HOSE, UPPER RADIATOR 174MMInstallation Diagram - Drawing No. 0F1020-A Section 9 - Installation DiagramMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE YOUR WARRANTY RIGHTS AND OBLIGATIONSPURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES CALIFORNIA EMISSION CONTROL WARRANTY STATEMENTEMISSION RELATED PARTS INCLUDE THE FOLLOWING EMISSION CONTROL SYSTEM WARRANTYWARRANTY SCHEDULE GENERAC POWER SYSTEMS TWO YEAR LIMITED WARRANTY FOR GUARDIANTHIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING GENERAC POWER SYSTEMS, INC P.O. BOX 297 WHITEWATER, WI