Generac Power Systems 005054-1 ‹ 4.8.8 CHECK FAN BELT, ‹ 4.8.9 INSPECT ENGINE GOVERNOR, Danger

Page 21
‹4.8.8 CHECK FAN BELT

Section 4 — Maintenance

Guardian Liquid-cooled 25 kW Generator

‹4.8.8 CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 of an inch. Adjust belt tension as required.

‹4.8.9 INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

7.Start engine and check for oil leaks.

‹4.8.11 CHANGING THE ENGINE AIR CLEANER

To replace the engine air cleaner, (part number 059402), simply remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover (Figure 4.1).

See the “Service Schedule,” for air cleaner mainte- nance.

‹ 4.8.12 SPARK PLUGS

‹4.8.9 INSPECT ENGINE GOVERNOR‹4.8.11 CHANGING THE ENGINE AIR CLEANER DANGER

DANGER: Do not attempt to adjust the gover-

!nor. Only qualified service facilities should adjust the governor. Excessively high operat- ing speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may short- en engine life. Correct rated frequency and voltage are supplied only at the proper gov- erned speed. Some connected electrical load devices may be damaged by incorrect fre- quency and/or voltage. Only qualified service technicians should adjust the governed speed.

Reset the spark plug gap or replace the spark plugs as necessary (Figure 4.4). See Section 6.

1.Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and com- mercial solvent. Do not blast the spark plugs to clean.

2.Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule,” Section 6, for recommended inspection.

3.Check the spark plug gap using a wire feeler gauge. Adjust the gap to 1.07-1.17 mm (0.042- 0.046 inch) by carefully bending the ground elec- trode (Figure 4.2).

‹4.8.10 CHANGING ENGINE OIL

Refer to maintenance performed by authorized service facilities for engine oil and filter change frequencies.

Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:

1.Remove OIL DRAIN HOSE from its retaining clip.

2.Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container.

3.When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip.

4.Turn OIL FILTER (Figure 4.1) counterclockwise and remove. Properly dispose of old filter.

5.Apply light coating of new engine oil to seal of new oil filter. Install FILTER and tighten by hand only.

DO NOT OVER TIGHTEN.

6.Remove OIL FILL CAP. Add recommended oil (see

SPECIFICATIONS). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is 4.0 U.S. quarts (3.8 liters).

After refilling the crankcase with oil, always

!check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.

Figure 4.4 – Setting the Spark Plug Gap

SET PLUG GAP AT 1.07 - 1.17 mm

(0.042 - 0.046 inch)

‹4.8.13 COOLANT CHANGE

Every year, have an Authorized Service Facility drain, flush and refill the cooling system. See “Specifications” for cooling system recommenda- tions.

Generac® Power Systems, Inc. 19

Image 21
Contents Owner’s Manual SHOULD ATTEMPT INSTALLATIONLiquid-cooled, Prepackaged Standby Generators This manual should remain with the unit‹ OPERATION AND MAINTENANCE AUTHORIZED SERVICE DEALER LOCATION‹ HOW TO OBTAIN SERVICE INTRODUCTIONGuardian Liquid-cooled 25 kW Generator Table of ContentsDespite the safe design of this generator GENERAL HAZARDSParts of the generator are rotating and/or hot during operation. Exercise care near running gen- eratorsFIRE HAZARDS ELECTRICAL HAZARDSEXPLOSION HAZARDS ‹ STANDARDS INDEX1.1 GENERATOR 1.2 TRANSFER SWITCH1.3 AUTOMATIC SYSTEM OPERATION 1.4 GENERATOR AC CONNECTION SYSTEMS‹ 1.7.2 HIGH COOLANT TEMPERATURE SWITCH ‹ 1.7.1 LOW OIL PRESSURE SWITCH‹ 1.7.3 LOW COOLANT LEVEL SWITCH Figure 1.4 - Low Oil Pressure Switch‹ 1.7.6 LOW BATTERY 1.10 SPECIFICATIONS‹ 1.8.1 UNPACKING PRECAUTIONS 1.8 UNPACKINGFigure 1.8 - Reconfigure the Fuel System 1.12 RECONFIGURING THE FUEL SYSTEM FOR LP VAPOR1.11 FUEL CONSUMPTION ‹ 1.10.2 GENERATOR2.1 STANDBY GENERATOR INSTALLATION 1.15 BEFORE INSTALLATION1.13 ENGINE OIL RECOMMENDATIONS 1.14 COOLANT RECOMMENDATIONS2.4 BASIC STANDBY ELECTRIC SYSTEM 2.3 GENERATOR MOUNTING AND SUPPORT2.2 GENERATOR LOCATION ‹ 2.1.2 OTHER PUBLISHED STANDARDS2.5 EMERGENCY CIRCUIT ISOLATION METHOD 2.9 USING AN ENGINEERED “GTS” TRANSFER SWITCH2.6 TOTAL CIRCUIT ISOLATION METHOD 2.7 GROUNDING THE GENERATORPos2 OFF - Standard Prepackaged ATS Application 2.10 BATTERY INSTALLATION‹ 2.10.1 VENTED BATTERIES Standby generators installed with automatic‹ 2.11.2 TRANSFER SWITCH 3.1 ENGINEERED GTS TRANSFER SWITCH2.11 PREPARATION BEFORE START-UP ‹ 2.11.1 PRIOR TO INITIAL START-UP‹ 3.2.1 AUTO/OFF/MANUAL SWITCH ‹ 3.2.2 FAULT INDICATOR LEDS‹ 3.2.5 SET EXERCISE TIME SWITCH 3.2 CONTROL CONSOLE COMPONENTS3.4 ENGINE GOVERNOR ADJUSTMENTS 3.3 MANUAL TRANSFER AND START-UP‹ 3.2.6 SYSTEM READY LED Figure 3.3 - “Set Exercise Time” Switch Figure 3.2 - Engine Governor Adjustment3.6 AUTOMATIC OPERATION 3.7 WEEKLY EXERCISE CYCLE4.1 MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES 3.8 CONTROL BOARD DIP SWITCH SETTINGSA. EVERY THREE MONTHS B. ONCE EVERY SIX MONTHS4.3 INTAKE MANIFOLD PROCEDURE 4.2 EXHAUST MANIFOLD PROCEDURE4.4 CYLINDER HEAD PROCEDURE Figure 4.1 - Intake Manifold Installation4.8 MAINTENANCE OWNER/ OPERATOR CAN PERFORM 4.6 OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM4.7 CHECKING FLUID LEVELS Figure 4.4 - Setting the Spark Plug Gap ‹ 4.8.11 CHANGING THE ENGINE AIR CLEANER‹ 4.8.8 CHECK FAN BELT ‹ 4.8.9 INSPECT ENGINE GOVERNOR‹ 4.9.1 CLEANING THE GENERATOR 4.9 MISCELLANEOUS MAINTENANCE‹ 4.9.2 BATTERY ‹ 4.9.3 BATTERY MAINTENANCEService Maintenance Interval Information 4.10 SCHEDULED MAINTENANCETurn off the battery charger turn OFF utility supply to ATS Remove the negative battery cableMaintenance LevelTasks Maintenance PROBLEM TROUBLESHOOTING POINTSCAUSE CORRECTIONGuardian Liquid-cooled 25 kW Generator Wiring Diagram - 2.5L Engine 15kW & 20kW units -Drawing No. 0F1411 26 Generac Power Systems, IncSection 7 - Electrical Data Section 7 - Electrical Data 28 Generac Power Systems, Inc Section 7 - Electrical Data 30 Generac Power Systems, Inc Wiring Diagram - 2.5L Engine 25kW unit -Drawing No. 0E9982-BSection 7 - Electrical Data 32 Generac Power Systems, Inc Electrical Schematic - 2.5L 25kW unit - Drawing No. 0E9983-BSection 7 - Electrical Data 34 Generac Power Systems, Inc HARNESS WIREMOUNT BLOCK ENGINEDESCRIPTION GROUND WIRE PANEL FOR ACCESSCOVER CABLE FASTENER TO SECUREEnclosure - Drawing No. 0E9720-D 38 Generac Power Systems, Inc HINGE CONTINUOUS 1.5L CTRL PNL 40 Generac Power Systems, Inc DESCRIPTION Guardian Liquid-cooled 25 kW Generator Engine - Drawing No. 0E9918-E 42 Generac Power Systems, IncSTEPPER MOTOR UNITS ONLY TO RADIATORGASKET, 2.5L FORD EXHAUST MAN SOURCE GENERAC-BOSCH GOVSERPENTINE BELT - 41 3/8 LENGTH BRKT,D.C. ALTERNATORMACHINEDTO ENGINE 0E1028A I/NCOVER 44 Generac Power Systems, IncSection 8 - Exploded Views and Parts LEADS LOCKTIGHT46 Generac Power Systems, Inc Alternator - Drawing No. 0E8660-CROTOR 390 30KW 1P DIRECT HSB 3.0L FORD & 2.5L FORD ROTOR REPLACEMENT PARTSSTR 390 35AD1 HSB 382MM LONG3.0L FORD & 2.5L FORD CONDUIT FLEX 1-1/4 30 LG - 3.0L FORD & 3.9L CHRYSLERSCREW HHC M8-1.25 X 60 G8.8 FT 48 Generac Power Systems, IncITEM 13 NEOPRENE SECURE WIRE HARNESSCOATING WITH TIE WRAP AS SHOWN1024 50 Generac Power Systems, IncSUPPORT,RADIATOR 2.5L FORD HOSE, UPPER RADIATOR 174MMInstallation Diagram - Drawing No. 0F1020-A Section 9 - Installation DiagramMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE YOUR WARRANTY RIGHTS AND OBLIGATIONSPURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES CALIFORNIA EMISSION CONTROL WARRANTY STATEMENTEMISSION RELATED PARTS INCLUDE THE FOLLOWING EMISSION CONTROL SYSTEM WARRANTYWARRANTY SCHEDULE GENERAC POWER SYSTEMS TWO YEAR LIMITED WARRANTY FOR GUARDIANTHIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING GENERAC POWER SYSTEMS, INC P.O. BOX 297 WHITEWATER, WI