Page 31

Section 2 – Installation

Wiring must be of adequate size, have approved insulative qualities and be properly supported.

Conduit and wire openings into the generator com- partment (if used) must be vapor-sealed to prevent entry of flammable, explosive or poisonous gases into the vehicle.

Recreational Vehicle Generator

Figure 2.13 – Generator AC Output Leads

483.1

REMOTE PANEL

CONNECTOR

‹2.6.1 ELECTRICAL JUNCTION BOX

Install an approved, square electrical junction box with a blank cover on the interior or exterior wall of the area planned for installation of the generator (NOT on the generator). Route the generator's AC output leads into this junction box through approved flexible conduit. This is the point of first termination for generator AC output leads.

‹ 2.6.2 WIRING

AC OUTPUT

HARNESS

FUEL FILTER

BATTERY

CONNECTIONS

Wiring should be of stranded copper to reduce the chance that vibration may cause breakage.

Wire gauge size should be large enough to handle at least 115 percent of the installed generator's rated maximum current.

Neutral conductors must be the same size as other leg wires.

Route power supply conductors from generator AC output leads (white), (black) and the green ground wire through approved flexible conduit to the elec- trical junction box on the compartment wall.

If flexible metal conduit is used between the gen- erator and the compartment junction box, the con- duit end that terminates the compartment junction box must be vapor-sealed. Flexible metal conduit is NOT vapor tight along its entire length.

From the junction box, route power supply wires through approved conduit to either (a) double-pole, double-throw transfer switch, or (b) approved iso- lation receptacle. Connecting to a transfer switch or isolation receptacle must prevent vehicle electri- cal circuits from being connected to two different power supplies at the same time (such as genera- tor and dockside power).

Conductors must be rated 221° F (105° C) or must be of a larger conductor size.

‹2.6.3 GENERATOR AC CONNECTIONS

Generator AC output leads (BLACK) “hot” and (WHITE) grounded neutral come out of the generator as shown in Figure 2.13. There is also a green lead that connects to ground in the junction box of the recreational vehicle.

Leads BLACK to WHITE are protected against over- load by a 30-amp circuit breaker (CB1). Use this line-to-neutral connection separately to operate 120- volt, single-phase, 60 Hertz, AC loads requiring up to 3,600 watts (3.6 kW) of power.

Do NOT connect electrical loads in excess of any circuit breaker rating or problems will develop with circuit breaker tripping, which causes a loss of AC output. Also, do NOT exceed the gener- ator's rated wattage capacity. Add the watts or amperes of all lighting, appliance, tool and motor loads the generator will operate at one time. This total should be less than the unit's rated wattage/amperage capacity.

‹2.6.4 CONDUIT

Route the connections between the generator and the junction box through approved, flexible conduit. The following general rules apply:

Cut wiring to the required length and allow extra wire for junction box connections.

Carefully prepare conduit ends to prevent sharp edges from cutting through wiring insulation.

Route conduit so it does not interfere with genera- tor movement.

If using metallic conduit, vapor seal the end of the conduit where it enters the junction box. Do this because flexible metallic conduit is not vaporproof along its entire length.

29

Image 31
Contents Air-cooled Recreational Vehicle Generators Introduction Authorized Service Dealer LocationInside Front Cover Part II Installation Instructions Warning   Electrical Hazards  Model Generator IdentificationGenerator AC Connection System SafetySpecifications Generator Applicability‹ 1.5.6 Emissions Compliance Period ‹ 1.5.5 Generator‹ 1.5.2 Fuel Consumption ‹ 1.5.3 Engine OIL RequirementsBefore Starting the Engine Generator Control PanelOptional Remote START/STOP Panel Automatic Choke‹ 2.4.4 Cooling and Ventilating AIR Starting the Generator‹ 2.4.2 Engine Lubrication ‹ 2.4.3 Fuel SupplyDo not Overload Generator Stopping the GeneratorProtection Systems ‹ 2.9.4 Overvoltage Protection Additional Information‹ 2.9.3 Field Boost ‹ 2.10.1 25-HOUR BREAK-IN Period‹ 2.10.5 Effects of Moisture and Dirt Checking the Engine OIL LevelChanging the Engine OIL AND/OR OIL Filter ‹ 2.10.4 Operation in High Grass or Brush‹ 3.3.1 Cleaning the Foam Precleaner Maintaining the Engine AIR CleanerFuel Filter Clean AIR IntakeClean Spark Arrestor Checking the Engine Spark Plug‹ 3.9.2 Every SIX Months Cleaning the GeneratorBattery Maintenance ‹ 3.9.1 Weekly‹ 3.12.2 Return to Service OUT of Service ProcedureAdjusting Valve Clearance ‹ 3.12.1 Removal from ServiceTightening Jam Nut RV Generator Service IntervalPart  General Hazards   Fire Hazards  Standards Booklets Purpose and Scope ManualEquipment Description Generator Engine Operating Speed0D8716 ‹ 2.1.1 Generator Location Location and Support‹ 2.1.2 Generator Support ‹ 2.2.1 Compartment Size Generator Compartments‹ 2.1.4 Generator Restraint ‹ 2.2.2 Compartment Construction‹ 2.2.3 Sound Insulating Materials ‹ 2.2.4 AcousticsView from TOP ‹ 2.2.5 Compartment Floor CutoutsCooling and Ventilating AIR ‹ 2.3.1 Generator Airflow ‹ 2.3.2 Testing the InstallationGasoline Fuel System Rigid Fuel Lines Exhaust System‹ 2.4.1 Fuel Tank ‹ 2.4.2 Generator Fuel Supply LineElectrical Connections ‹ 2.5.2 Exhaust System Safety‹ 2.5.1 Spark Arrestor ‹ 2.6.4 Conduit ‹ 2.6.2 Wiring‹ 2.6.1 Electrical Junction BOX ‹ 2.6.3 Generator AC Connections‹ 2.6.6 Power Supply Cord ‹ 2.6.5 Isolating Different Power Sources‹ 2.7.3 Battery Cable Connections Battery Installation‹ 2.7.1 Recommended Battery ‹ 2.7.2 Battery CablesBefore Initial START-UP Post Installation TestsTesting Under Load Initial StartInstallation Checklist Appendix 1 Notes Problem Cause Correction Troubleshooting GuideAppendix 3 Electrical Data Supplied by Customer To Carb Part NO. QTY Description 21 2 QTY Description 274 Regulator Voltage Appendix 4 Exploded Views and Parts Lists GUARD, FAN Appendix 4 Exploded Views and Parts Lists Long Block Assembly MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule CONSUMER/PERSONAL Applications

004700-00 specifications

Generac Power Systems is a recognized leader in the field of backup power generation, and one of its standout products is the Generac 004700-00. This reliable and high-performance generator has garnered attention for its robust features and advanced technological capabilities, making it an appealing choice for homeowners and businesses alike.

One of the key features of the Generac 004700-00 is its ability to deliver a reliable source of power during outages. With a powerful engine, this generator is designed to handle substantial loads, including sensitive electronics, heating systems, and appliances without compromising performance. The generator achieves this with a recommended horsepower rating that ensures a steady output even under heavy demand.

Incorporating Generac’s advanced Synch Power technology, the 004700-00 enables users to operate multiple devices simultaneously without any disruption. This feature ensures that the power provided is stable and consistent, minimizing the risk of damage to electronic devices during surges or fluctuations. Furthermore, the generator is engineered with a user-friendly control panel, making it easy to monitor performance metrics and adjust settings as necessary.

A standout characteristic of the 004700-00 is its quiet operation. Unlike many traditional generators, this unit utilizes noise-reducing technologies, ensuring that it operates at a lower decibel level. This feature is particularly beneficial for residential areas, where noise restrictions may be a concern.

The Generac 004700-00 also excels in fuel efficiency, allowing it to run longer on less fuel. This is achieved through its advanced engine design and efficient fuel consumption rate, which not only saves on operating costs but also reduces the environmental impact. Additionally, the generator is compatible with various fuel types, enhancing its versatility and convenience for users.

Ease of maintenance is another consideration with the 004700-00, as it is equipped with a maintenance alert system that notifies users when service is required. This proactive approach to care ensures that the generator remains in optimal working condition, prolonging its lifespan and reliability.

In summary, the Generac Power Systems 004700-00 stands out with its powerful performance, advanced technology, quiet operation, fuel efficiency, and user-friendly features. Whether for residential or commercial use, this generator provides a dependable solution for anyone in need of backup power when it matters most.