Generac Power Systems 004700-00 Initial Start, Post Installation Tests, Before Initial START-UP

Page 34

Section 3 – Post-Installation Start-up Adjustments

Recreational Vehicle Generator

‹2.8.1 REMOTE START/STOP PANEL

3.3INITIAL START

A remote mounted Start/Stop panel (Figure 2.18) is available that allows the user to start and stop the generator engine conveniently from inside the vehicle. The remote panel includes a Start/Stop switch, hour- meter, generator run lamp, a fuel prime switch, and a wire harness. The hourmeter should be used in conjunction with the maintenance operations found in Part I of this manual.

Figure 2.18 – Optional Remote Panel

FUEL

RUN

PRIME

STOP

3.1POST INSTALLATION TESTS

The air-cooled generator set was factory tested and adjusted. It should not be required to adjust the unit any further except under special circumstances.

Do not make any unnecessary adjustments. Factory settings are correct for most applica- tions. When making adjustments, however, be careful to avoid overspeeding the engine.

3.2BEFORE INITIAL START-UP

Before starting, complete the following:

1.Check the engine crankcase oil level and, if nec- essary, fill to the dipstick “FULL” mark (cross- hatched area) with the recommended oil. Do not fill above the FULL mark.

2.Check the fuel supply. Gas fuel lines must have been properly purged and leak tested in accor- dance with applicable fuel codes. All fuel shutoff valves in the fuel supply lines must be open.

DANGER

If a liquid propane (LP) gas fuel system has been installed, it must be properly tested for leaks before operating the system in compliance with ANSI A119.2/NFPA 501C. No leakage is permit- ted. Be sure that no gasoline fuel vapors enter the vehicle interior.

32

When absolutely certain that the unit has been prop- erly installed and prepared for use, start the engine as follows:

1.Turn off all electrical loads. Do this by setting the generator’s main circuit breakers to their “OFF” (or open) position.

2.Refer to Part I, Section 2.5, “Starting the Generator”, for cranking and starting instruc- tions. The engine may require more cranking for initial starting since the fuel lines have to be primed (use of the primer switch will shorten this time).

3.Let the engine warm up for about five minutes to allow internal temperatures to stabilize.

4.Carefully inspect the engine/generator for fuel, oil and exhaust system leaks. Before proceeding to the next step, correct any leakage immediately.

5.When all tests and adjustments at no-load are completed, apply electrical loads and check for proper operation under load. See Section 3.4. Run the unit at least 30 minutes with loads applied.

6.Turn off all electrical loads by setting the gener- ator’s main circuit breakers to their “OFF” (or open) position.

7.Let the unit run at no-load for a few minutes to stabilize internal engine/generator temperatures. Then, shut down the engine.

NOTE:

The generator set was thoroughly tested and adjusted at the factory before shipping. No addi- tional adjustment should be necessary. Only quali- fied service technicians who have been trained should perform adjustments outlined in this manual.

3.4TESTING UNDER LOAD

Apply electrical loads equal to about 75 to 100 per- cent of the unit's rated wattage/amperage capacity.

Let the unit run at least 30 minutes with load applied. During this part of the test, check that the unit is not running excessively hot and that adequate cooling airflow is available. Do not allow the unit to overheat during prolonged operation.

NOTE:

The generator engine is equipped with a high tem- perature switch. The switch has normally closed (N.C.) contacts. When the engine temperature is too high, switch contacts close, and the engine shuts down automatically.

THE MANUFACTURER RECOMMENDS THAT THE GENERATOR BE TESTED FOR ADEQUATE COOL- ING.

Image 34
Contents Air-cooled Recreational Vehicle Generators Authorized Service Dealer Location IntroductionPart II Installation Instructions Inside Front Cover Warning   Electrical Hazards  Generator Identification ModelGenerator Applicability SafetySpecifications Generator AC Connection System‹ 1.5.3 Engine OIL Requirements ‹ 1.5.5 Generator‹ 1.5.2 Fuel Consumption ‹ 1.5.6 Emissions Compliance PeriodAutomatic Choke Generator Control PanelOptional Remote START/STOP Panel Before Starting the Engine‹ 2.4.3 Fuel Supply Starting the Generator‹ 2.4.2 Engine Lubrication ‹ 2.4.4 Cooling and Ventilating AIRDo not Overload Generator Stopping the GeneratorProtection Systems ‹ 2.10.1 25-HOUR BREAK-IN Period Additional Information‹ 2.9.3 Field Boost ‹ 2.9.4 Overvoltage Protection‹ 2.10.4 Operation in High Grass or Brush Checking the Engine OIL LevelChanging the Engine OIL AND/OR OIL Filter ‹ 2.10.5 Effects of Moisture and DirtMaintaining the Engine AIR Cleaner ‹ 3.3.1 Cleaning the Foam PrecleanerChecking the Engine Spark Plug Clean AIR IntakeClean Spark Arrestor Fuel Filter‹ 3.9.1 Weekly Cleaning the GeneratorBattery Maintenance ‹ 3.9.2 Every SIX Months‹ 3.12.1 Removal from Service OUT of Service ProcedureAdjusting Valve Clearance ‹ 3.12.2 Return to ServiceRV Generator Service Interval Tightening Jam NutPart  General Hazards   Fire Hazards  Generator Engine Operating Speed Purpose and Scope ManualEquipment Description Standards Booklets0D8716 ‹ 2.1.1 Generator Location Location and Support‹ 2.1.2 Generator Support ‹ 2.2.2 Compartment Construction Generator Compartments‹ 2.1.4 Generator Restraint ‹ 2.2.1 Compartment Size‹ 2.2.4 Acoustics ‹ 2.2.3 Sound Insulating Materials‹ 2.2.5 Compartment Floor Cutouts View from TOPCooling and Ventilating AIR ‹ 2.3.1 Generator Airflow ‹ 2.3.2 Testing the InstallationGasoline Fuel System ‹ 2.4.2 Generator Fuel Supply Line Exhaust System‹ 2.4.1 Fuel Tank Rigid Fuel LinesElectrical Connections ‹ 2.5.2 Exhaust System Safety‹ 2.5.1 Spark Arrestor ‹ 2.6.3 Generator AC Connections ‹ 2.6.2 Wiring‹ 2.6.1 Electrical Junction BOX ‹ 2.6.4 Conduit‹ 2.6.5 Isolating Different Power Sources ‹ 2.6.6 Power Supply Cord‹ 2.7.2 Battery Cables Battery Installation‹ 2.7.1 Recommended Battery ‹ 2.7.3 Battery Cable ConnectionsInitial Start Post Installation TestsTesting Under Load Before Initial START-UPInstallation Checklist Appendix 1 Notes Troubleshooting Guide Problem Cause CorrectionAppendix 3 Electrical Data Supplied by Customer To Carb Part NO. QTY Description 21 2 QTY Description 274 Regulator Voltage Appendix 4 Exploded Views and Parts Lists GUARD, FAN Appendix 4 Exploded Views and Parts Lists Long Block Assembly MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule CONSUMER/PERSONAL Applications

004700-00 specifications

Generac Power Systems is a recognized leader in the field of backup power generation, and one of its standout products is the Generac 004700-00. This reliable and high-performance generator has garnered attention for its robust features and advanced technological capabilities, making it an appealing choice for homeowners and businesses alike.

One of the key features of the Generac 004700-00 is its ability to deliver a reliable source of power during outages. With a powerful engine, this generator is designed to handle substantial loads, including sensitive electronics, heating systems, and appliances without compromising performance. The generator achieves this with a recommended horsepower rating that ensures a steady output even under heavy demand.

Incorporating Generac’s advanced Synch Power technology, the 004700-00 enables users to operate multiple devices simultaneously without any disruption. This feature ensures that the power provided is stable and consistent, minimizing the risk of damage to electronic devices during surges or fluctuations. Furthermore, the generator is engineered with a user-friendly control panel, making it easy to monitor performance metrics and adjust settings as necessary.

A standout characteristic of the 004700-00 is its quiet operation. Unlike many traditional generators, this unit utilizes noise-reducing technologies, ensuring that it operates at a lower decibel level. This feature is particularly beneficial for residential areas, where noise restrictions may be a concern.

The Generac 004700-00 also excels in fuel efficiency, allowing it to run longer on less fuel. This is achieved through its advanced engine design and efficient fuel consumption rate, which not only saves on operating costs but also reduces the environmental impact. Additionally, the generator is compatible with various fuel types, enhancing its versatility and convenience for users.

Ease of maintenance is another consideration with the 004700-00, as it is equipped with a maintenance alert system that notifies users when service is required. This proactive approach to care ensures that the generator remains in optimal working condition, prolonging its lifespan and reliability.

In summary, the Generac Power Systems 004700-00 stands out with its powerful performance, advanced technology, quiet operation, fuel efficiency, and user-friendly features. Whether for residential or commercial use, this generator provides a dependable solution for anyone in need of backup power when it matters most.