SERVICE MANUAL SPLIT TYPE
CONTENTS
Page
Original instruction
Generic Denomination: Air Conditioner Definition of Qualified Installer or Qualified Service Person
Definition of Protective Gear
[Explanation of indications]
[Explanation of illustrated marks]
DANGER WARNING CAUTION
Warning Indications on the Air Conditioner Unit
[Confirmation of warning label on the main unit]
ELECTRICAL SHOCK HAZARD
BURST HAZARD
WARNING
Precaution for Safety
DENGER
WARNING
Page
Page
Page
Explanations given to user
Relocation
Declaration of Conformity
Page
New Refrigerant (R410A)
1. Safety Caution Concerned to New Refrigerant
2. Cautions on Installation/Service
3. Pipe Materials
1) Copper pipe <Piping>
Q R S T U V W X Y
General tools (Conventional tools can be used.)
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
1. AIR DUCTING WORK
1-1. Static Pressure Characteristics
Fig. 4 SM80 type (Square duct)
Fig. 2 SM56 type (Square duct)
RAV-SN564BT
Fig. 5 SM110 type (Round duct)
Fig. 6 SM110 type (Square duct)
Fig. 8 SM140 type (Square duct)
Fig. 7 SM140 type (Round duct)
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. Compact 4-way Cassette Type
RAV-SM404MUT
Space required for installation and servicing
2-2. Concealed Duct Type
Page
Page
Page
4. SPECIFICATIONS OF ELECTRICAL PARTS
4-1. Compact 4-way Cassette Type
4-2. Concealed Duct Type
4-3. Ceiling Type
5. CONTROL BLOCK DIAGRAM
5-1. Indoor Controller Block Diagram
*
1:1 model connection interface
5-1-1. In Case of Connection of Wired (Simple) Remote Controller
5-1-2. In Case of Connection of Wireless Remote Controller
Wireless remote controller
1:1 model connection interface (Option)
Indoor unit #1 (Heder)
*
5-1-3. Connection of Both Wired (Simple) Remote Controller and Wireless Remote Controller
*
1:1 model connection interface
Indoor unit #1 (Heder)
5-2. Control Specifications
Page
Page
Page
5 2
C
A J
I
Q R
Page
Page
Page
Page
2 3
5 6 7
23, 4, 5,
6
2, 7
Be sure to set the air speed to [High]
Page
Page
Q
R
S
5-3. Indoor Print Circuit Board
5-3-1. Compact 4-way Cassette Type / Concealed Duct Type / Ceiling Type
<MCC-1402>
Indoor P.C. Board Optional Connector Specifications (MCC-1402)
6. TROUBLESHOOTING
6-1. Summary of Troubleshooting
<Wired remote controller type>
1. Before troubleshooting
+
1. Before troubleshooting
+
2. Troubleshooting procedure
Outline of judgment
Page
Page
47
6-2. Check Code List (Indoor)
(Indoor unit detected)
(Remote controller detected)
(Central control devices detected)
Check Code List
Error mode detected by indoor unit
Error mode detected by outdoor unit
Page
Error mode detected by remote controller or central controller (TCC-LINK)
6-3. Diagnostic Procedure for Each Check Code (Indoor Unit)
Check code [E01 error]
[E09 error]
[E04 error]
[E10 error]
[E18 error]
[E08, L03, L07, L08 error]
[L09 error]
[L20 error]
[L30 error]
[P30 error] (Central controller)
[P10 error]
Check that voltage of 1 3 pin of CN068 on the indoor P.C. board is 220240V.
[F10 error]
[P12 error]
CN333
CN334
[P19 error]
Operation check direction of the outdoor P.C. board (In case of self-preservation valve)
Check by tester
[F02 error]
[F01 error]
[C06 error] (1:1 model connection interface)
1
[E03 error] (Master indoor unit)
[F29 error]
[P31 error] (Follower indoor unit)
TA, TC, TCJ, TE, TS, TO sensor
Temperature Resistance value characteristic table
TD, TL sensor
Representative value
TA, TC, TCJ, TE, TS, TO sensor
TD, TL sensor
Winding Resistance of Fan Motor
Page
[2] P.C. Board for indoor unit servicing replacement procedures
[1] Setting data read out from EEPROM
CODE No. required at least
MCC-1402
[3] Writing the setting data to EEPROM
3651 42
<Fig. 1 RBC-AMT32E>
<Fig. 2 EEPROM layout diagram>
Table 2. Type: CODE No. 10 Table 3. Indoor unit capacity: CODE No. 11
EEPROM initial value on the P.C. board for indoor unit servicing.
Table 1
8. SETUP AT LOCAL SITE AND OTHERS
8-1. Indoor Unit
1
2
3
4
and return Dip switch of the sensor section as before.
23, 4, 5, 6 2, 7
1
2
6
5
4
1
<Procedure> Perform setting while the air conditioner stops.
5
4
3
Item No. (DN) table (Selection of function)
Page
8-1-5. Cabling and Setting of Remote Controller Control
(Setup method)
2-remote controller control (Controlled by 2 remote controllers)
BA
When connected 2 remote controllers operate an idoor unit
1
Returned to usual display
4
<Contents>
+
1
button returns the display to usual display.
<Contents>
1 2 3
3
nIndoor unit power-ON sequence
1:1 model connection interface P.C. board MCC-1440
( )
Indoor unit
8-2. Setup at Local Site / Others
Model name: TCB-PCNT30TLE
8-2-1. 1:1 Model Connection Interface (TCC-LINK adapter)
1. Function
This model is an optional P.C. board to connect the indoor unit to 1:1 model connection interface.
( )
(Reference) Setup contents of switch
6. External view of P.C. board assembly
1
O
/
O
TEMP.
Page
( ) ( )
9. ADDRESS SETUP
9-1. Address Setup
<Address setup procedure>
9-2. Address Setup & Group Control
<Terminology>
9-2-1. System configuration
Page
Single Twin Triple
9-2-2. Automatic Address Example from Unset Address (No miswiring)
1. Standard (One outdoor unit)
Only turning on source power supply (Automatic completion) 3. Multiple groups operation
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11
1
3, 6, 9
END 11
2, 5, 8 4, 7, 10
1 2 3
<Operation procedure>
3
1 2
2
MUT
10-1. Compact 4-Way Cassette Type
Ceiling panel: RBC-UM11PG(W)E Preparing work:
Page
Page
Page
Page
Page
Page
Page
Page
10-2. Concealed Duct Type
BT
Be sure to turn off the power supply or circuit breaker before disassembling work
R
Q
Page
Page
10-3. Ceiling Type
CT
Be sure to turn off the power supply or circuit breaker before disassembling work
Page
Page
Page
Page
Page
Page
Electric parts
401 405
403 404 402
11-2. Concealed Duct Type
Page
Page
Page
Page
Page
Page
11-3. Ceiling Type
Page
Page
403 401
Electric parts
407
406
404405402
WARNINGS ON REFRIGERANT LEAKAGE
NOTE 3 :
Check of Concentration Limit
NOTE 1 :
Important