Toshiba CONCEALED DUCK TYPE, CEILING TYPE 37, Item, Outline of specifications, Remarks

Models: CONCEALED DUCK TYPE CEILING TYPE

1 120
Download 120 pages 7.39 Kb
Page 37
Image 37
– 37 –

No.

Item

 

Outline of specifications

Remarks

 

 

 

 

 

15

Central control

1)

Setting at the central controller side enables to select

 

 

mode selection

 

the contents which can be operated on the wired

 

 

 

 

remote controller.

 

 

 

2)

Setup contents

 

In case of TCC-LINK Central remote controller (TCB-SC642TLE2)

[Individual]:

Operated by wired remote controller

Display at wired remote

([After-push precedence])

controller side (No display)

[Central 1]:

[

 

] goes on.

START / STOP operation by wired remote controller

 

 

 

is unavailable.

 

 

 

[Central 2]:

[

 

] goes on.

START / STOP, MODE change and TEMP. setting by

 

 

 

wired remote controller are unavailable.

 

 

 

[Central 3]:

[

 

] goes on.

MODE change and TEMP. setting by wired remote

 

 

 

controller are unavailable.

 

 

 

[Central 4]:

[

 

] goes on.

MODE change by wired remote controller is

 

 

 

unavailable.

 

 

 

In case of the wireless remote controller, the con- tents to be operated are same though the display lamp does not change.

If an item prohibited by the central control mode is operated from the remote controller, it is notified with receiving sound Pi, Pi, Pi, Pi, Pi (5 times)

16

Energy-saving

1)

Selecting [AUTO] mode enables an energy-saving to

 

 

 

control

 

be operated.

 

 

 

 

 

 

2)

The setup temperature is shifted (corrected) in the

 

 

 

 

 

range not to lose the comfort ability according to input

 

 

 

 

 

values of various sensors.

 

 

 

 

 

 

3)

Data (Input value room temp. Ta, Outside temp. To, Air

 

 

 

 

 

volume, Indoor heat exchanger sensor temp. Tc) for

 

 

 

 

 

20 minutes are taken the average to calculate correc-

 

 

 

 

 

tion value of the setup temperature.

 

 

 

 

 

 

4)

The setup temperature is shifted every 20 minutes,

 

 

 

 

 

and the shifted range is as follows.

 

 

 

 

 

 

 

In cooling time: +1.5 to – 1.0K

 

 

 

 

 

 

 

In heating time: –1.5 to +1.0K.

 

 

 

 

 

 

 

 

17

Max. frequency

1)

This control is operated by selecting [AUTO] operation mode.

 

cut control

2)

COOL operation mode:

3) HEAT operation mode:

 

 

 

 

 

It is controlled according to the following

It is controlled according to the following

 

 

 

figure if To < 28°C.

figure if To > 15°C.

 

 

 

 

 

 

 

Max. frequency is

 

 

 

Ta ˚C

Ta ˚C

restricted to approximately

 

 

 

Normal control

 

 

 

the rated heating frequency

 

 

 

+4

 

Tsh

 

 

 

 

 

 

+3

 

–3

 

 

 

 

 

 

 

 

 

 

 

Tsc

 

–4

 

 

 

 

 

 

 

 

 

 

 

Max. frequency is

Normal control

 

 

 

restricted to approximately

 

 

 

 

 

the rated cooling frequency

 

 

– 37 –