Toshiba CONCEALED DUCK TYPE Item, Outline of specifications, Remarks, In cooling/dry operation

Models: CONCEALED DUCK TYPE CEILING TYPE

1 120
Download 120 pages 7.39 Kb
Page 33
Image 33
In cooling/dry operation

No.

Item

Outline of specifications

Remarks

 

 

 

 

 

12

Louver control:

1) Louver position setup

 

 

 

Compact 4-way

• When the louver position is changed, the position moves

 

 

type only

 

 

necessarily to downward discharge position once to return to

 

 

 

the set position.

 

 

 

 

• The louver position can be set up in the following operation range.

 

 

 

In cooling/dry operation

In heating/fan operation

 

In group twin/triple operation, the louver positions can be set up collectively or individually.

2) Swing setup

The swinging

• [SWING] is displayed and the following display is repeated.

louver moves

In all operations

usually up to the

ceiling side from

 

 

the louver position

 

of the set time.

(Repeats)

In group twin operation, the louver positions can be set up collectively or individually.

3)When the unit stopped or the warning was output, the louver is automatically set to full closed position.

4)When PRE-HEAT In heating/fan operation (Heating ready) is displayed

(Heating operation started or defrost operation is performed), heating thermo is off or self-cleaning is performed, the louver is automatically set to horizontal discharge position.

The louver which air direction is individually set or the locked louver closes fully when the unit stops and the louver is automatically set to horizontal discharge position when PRE-HEAT In all operations (Heating ready) is displayed, heating thermo is off or self-cleaning is performed.

– 33 –

Page 33
Image 33