UNIT LOUVER

9-4. Confirmation of Indoor Unit No. Position

1. To know the indoor unit addresses though position of the indoor unit body is recognized

In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation)

<Procedure>

 

1

Push ON / OFF

button if the unit stops.

2

Push UNIT LOUVER

button.

Unit No. 1-1is displayed on LCD. (It disappears after several seconds.)

The displayed unit No. indicate line address and indoor unit address. (When other indoor units are connected to the identical remote controller (Group control unit), other unit numbers are also displayed every pushing UNIT LOUVER button.

TEMP.

 

 

ON / OFF

 

TIMER SET

FAN

MODE

 

TIME

SAVE

VENT

FILTER

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

1

Operation

<Operation procedure>

1 Manual background 2 END

2.To know the position of indoor unit body by address

To confirm the unit No. in the group control

(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)

2

<Procedure>

The indoor unit numbers in the group control are successively displayed, and fan, louver, and drain pump of the corresponding indoor unit are turned on.

(Follow to the procedure during operation)

1 Push VENT and TEST buttons simultaneously for 4 seconds or more.

Unit No. Manual backgroundManual background is displayed.

Fans and louvers of all the indoor units in the group control operate.

2 Every pushing button, the unit numbers in the group control are successively displayed.

The unit No. displayed at the first time indicates the header unit address.

TEMP.

 

 

ON / OFF

1

 

TIMER SET

FAN

MODE

 

TIME

SAVE

VENT

 

 

 

FILTER

 

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

 

3

<Operation procedure>

2

• Fan and louver of the selected indoor unit only

1

 

2

 

3 END

 

 

operate.

3 Push TEST button to finish the procedure.

All the indoor units in the group control stop.