Toshiba CEILING TYPE, CONCEALED DUCK TYPE service manual 84, Example

Models: CONCEALED DUCK TYPE CEILING TYPE

1 120
Download 120 pages 7.39 Kb
Page 84
Image 84
(Example)

4.Single group operation

• Each indoor unit controls the outdoor unit individually.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-1

 

 

1-1

 

4-1

 

3-1

Header/Sub

 

Header/Sub

 

Header/Master

 

Header/Sub

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-1

Header/Sub

5. Multiple groups operation (Manual address setting)

2-1

Header/Sub

1-1

Header/Sub

1-2

Follower/Sub

3-1

Header/Master

3-2

Follower/Sub

3-3

Follower/Sub

• Master unit:

The master unit receives the indoor unit data (thermo status) of the sub

 

(Without identical line address & indoor/outdoor serial) and then finally controls the outdoor

 

compressor matching with its own thermo status.

 

The master unit sends this command information to the sub unit.

• Sub unit:

The sub unit receives the indoor unit data from the master (With identical line address & indoor/

 

outdoor serial) and then performs the thermo operation synchronized with the master unit.

 

The sub unit sends own thermo ON/OFF demand to the master unit.

 

(Example)

 

No. 1-1 master unit sends/receives signal to/from No. 1-2 and No. 1-3 sub units.

 

(It is not influenced by the line 2 or 3 address indoor unit.)

– 84 –

Page 84
Image 84
Toshiba CEILING TYPE, CONCEALED DUCK TYPE service manual 84, Example