UNIT LOUVER

8-1-4. Function Selection Setup

<Procedure> Perform setting while the air conditioner stops.

1 Push TEST + SET + CL buttons simultaneously for 4 seconds or more.

The first displayed unit No. is the master indoor unit address in the group control.

In this time, fan and louver of the selected indoor unit operate.

ò

2 Every pushing 4 button (button at left side), the indoor unit No. in the group control is displayed one after the other. In this time, fan and louver of the selected indoor unit only operate.

3

ò

Using the set temperature

TEMP. buttons, specify the CODE No. (DN).

4

ò

Using the timer time TIME

buttons, select the set data.

5

ò

Push SET button. (OK if indication lights)

 

• To change the selected indoor unit, proceed to Procedure 2 .

 

• To change item to be set up, proceed to Procedure 3 .

ò

6 Pushing TEST button returns the status to the normal stop status.

TEMPON / OFF

3

 

 

TIMER SET

FAN

MODE

6

 

 

 

 

 

FILTER

TIME

 

 

SAVE

VENT

 

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

1

<Operation procedure>

4

5

2