Indoor P.C. Board Optional Connector Specifications (MCC-1402)

Function

Connector

Pin

Specifications

Remarks

No.

No.

 

 

 

 

 

 

 

 

Option output

CN60

1

DC12V (COM)

 

 

 

 

 

 

 

 

2

Defrost output

ON during defrost operation of outdoor unit

 

 

 

 

 

 

 

3

Thermo. ON output

ON during Real thermo-ON (Comp ON)

 

 

 

 

 

 

 

4

Cooling output

ON when operation mode is in cooling system

 

 

 

 

(COOL, DRY, COOL in AUTO cooling/heating)

 

 

 

 

 

 

 

5

Heating output

ON when operation mode is in heating system

 

 

 

 

(HEAT, HEAT in AUTO cooling/heating)

 

 

 

 

 

 

 

6

Fan output

ON during indoor fan ON

 

 

 

 

(Air purifier is used/Interlock cable)

 

 

 

 

 

Outside error input

CN80

1

DC12V (COM)

(When continued for 1 minute)

 

 

 

 

Check code “L30” is output and forced operation stops.

 

 

2

DC12V (COM)

 

 

 

 

 

 

 

 

 

 

3

Outside error input

 

 

 

 

 

 

CHK

CN71

1

Check mode input

Used for operation check of indoor unit.

Operation check

 

 

 

(Communication with outdoor unit or remote controller

 

 

 

 

 

2

0V

is not performed, but the specified operation such as

 

 

 

 

indoor fan “H” or drain pump ON is output.)

DISP display mode

CN72

1

Display mode input

 

 

 

 

 

 

 

 

2

0V

Display mode enables indoor unit and remote controller

 

 

 

 

to communicate. (When power is turned on)

EXCT demand

CN73

1

Demand input

 

 

 

 

 

 

 

 

2

0V

Forced thermo-OFF operation in indoor unit

 

 

 

 

 