8-1-6. Monitor Function of Remote Controller

8-1-6. Monitor Function of Remote Controller

nCalling of sensor temperature display

<Contents>

Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by calling the service monitor mode from the remote controller.

<Procedure>

1

2

Push TEST + CL buttons simultaneously for 4 seconds to call the service monitor mode.

The service monitor goes on, the master indoor unit No. is displayed, at first and then the temperature of CODE No. ￿￿ is displayed.

Push temperature set nCalling of sensor temperature displayTEMP. buttons and then change the CODE No. of data to be monitored.

The item code list is shown below:

TEMP.

 

 

ON / OFF

 

 

TIMER SET

FAN

 

MODE

 

 

TIME

SAVE

 

VENT

FILTER

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4

1

3

<Operation procedure>

1 1  2  3  4 2 – 75 – 3 Manual background 4

Returned to usual display

 

CODE No.

Data name

Unit

 

 

 

 

 

01

Room temperature

°C

 

 

(Remote controller)

 

 

02

Indoor suction temperature (TA)

°C

data

03

Indoor heat exchanger (Coil)

°C

 

temperature (TCJ)

 

unit

 

 

04

Indoor heat exchanger (Coil)

°C

Indoor

 

temperature (TC)

 

07

Indoor fan revolution frequency

rpm

 

 

 

 

F2

Indoor fan calculated operation time

×100h

 

F3

Filter sign time

×1h

 

F8

Indoor discharge temperature

°C

 

 

 

 

Outdoor unit data

CODE No.

Data name

Unit

 

 

 

60

Outdoor heat exchanger (Coil) temperature (TE)

°C

61

Outside temperature (TO)

°C

62

Compressor discharge temperature (TD)

°C

63

Compressor suction temperature (TS)

°C

65

Heat sink temperature (THS)

°C

6A

Operation current (× 1/10)

A

6D

Outdoor heat exchanger (Coil) temperature (TL)

°C

70

Compressor operation frequency

rps

72

Outdoor fan revolution frequency (Lower)

rpm

73

Outdoor fan revolution frequency (Upper)

rpm

F1

Compressor calculated operation time

×100h

 

 

 

3

ò

Push UNIT LOUVER button to select the indoor unit to be monitored.

Each data of the indoor unit and its outdoor units can be monitored.

ò

4 Pushing TEST button returns the status to the usual display.

The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.