321 Studios FLR140D60E Appliances Located In Confined Spaces, All Air From Inside The Building

Models: FH110D60E FH085D36E FLR110D60E FLR085D36E FLR110D48E FC085D36E FLF110D60E FLF085D36E FLR140D60E FH110D48E FLF110D48E

1 39
Download 39 pages 2.46 Kb
Page 24
Image 24
APPLIANCES LOCATED IN CONFINED SPACES

APPLIANCES LOCATED IN CONFINED SPACES

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation, and dilution of flue gases. However, in buildings of unusually tight construction, additional air shall be provided using the method described under “All Air From Outdoors” in Figure 13.

An unconfined space (such as an open basement) must have a minimum volume of 50 cubic feet per 1,000 BTUH of total of all appliances in area. Adjoining rooms may be counted as one area only if there are not doors between the rooms.

Shown in Table 8 are the required minimum areas in square feet to qualify as an unconfined space for various total BTUH input ratings. The table is based on a room(s) with 8 foot ceiling heights.

If the unconfined space is within a building having insufficient air because of tight construction, the air for combustion and ventilation shall be obtained from outdoors or from spaces freely communicating with the outdoors. Under these conditions a permanent opening or openings have a total free area of not less than one square inch per 5,000 BTU per hour (28 square inches per hour ) of total input rating of all appliances shall be provided. For combustion air options see Page 20, “Combustion Air Requirements”.

FIGURE 12

APPLIANCES LOCATED

IN CONFINED SPACES

ALL AIR FROM INSIDE THE BUILDING

MIS-1336

TABLE 8

SQUARE FEET REQUIRED TO

QUALIFY AS UNCONFINED SPACE

Total

Unconfined Space

Minimum Area In

BTUH

Square Feet

Input

8' Ceiling Height

 

 

 

60,000

375

80,000

500

85,000

531

105,000

656

115,000

719

120,000

750

140,000

875

145,000

906

160,000

1000

200,000

1250

ALL AIR FROM INSIDE BUILDING

The confined space shall be provided with two permanent openings, one near the top of the enclosure and one near the bottom. Each opening shall have a free area of not less than one square inch per 1,000 BTU per hour (140 square inches per gallon per hour) of the total input rating of all appliances in the enclosure freely communicating with interior areas having in turn adequate infiltration from the outside. (See Figure 12.) Also see Table 9 on the following page for specific ventilation opening requirements for the furnace only.

The flow of combustion and ventilating air must not be obstructed from reaching the furnace.

NOTE: Each opening shall have a free area of not less than one square inch per 1,000 BTU per hour (140 square inches per gallon per hour) of the total input rating of all appliances in the enclosure.

Manual 2100-422

Page 22

Page 24
Image 24
321 Studios FLR140D60E, FLF110D48E, FH110D48E Appliances Located In Confined Spaces, All Air From Inside The Building