Example: A Genesis boiler is rated at 1,300,000 Btu/hr. input at sea level. At an altitude of 5,000 (1500m), the prejet orifices will decrease the input rate by 20% (= 4% x 5) to a new rating of 1,040,000 Btu/hr. (= 80% x 1,300,000 Btu/hr.) The input reduction is achieved by the prejet orifices through
FEATURES/CONTROLS
MULTI-STAGE FIRING AND CONTROL SYSTEM
ALL MODELS - The control system consists of three basic components: 1) Central Control Board 2) Ignition Control Board and 3) Display Board. The Central Control Board and Ignition Control Boards are located in the control box and can be accessed through panels on the left side and top of the unit. The Display Board is attached to the front jacket panel. The control system is a
The central control board contains a strip of dip switches which allow the user to control several system variables. Table 5 shows a summary of these options. Make sure the dip switches are in the appropriate position for the unit's application. Consult the Control System section of the manual for more information, see page 26.
DIP SWITCH CONFIGURATION TABLE
SW1 OFF | ON | SELECTION: |
| |
A | 3 STAGE | 4 STAGE | EITHER 3 OR 4 STAGE SYSTEM |
|
B | 3 TRIALS | 1 TRIAL | EITHER 3 OR 1 |
|
C | NOIRI | IRI | WHETHER SYSTEM IS IRI OR |
|
| GAS VALVE | GAS VALVE | STANDARD |
|
D | INLET | TANK | INLET OR TANK AS |
|
|
|
| CONTROLLING PROBE |
|
E | NO EXTERNAL EXTERNAL | WHETHER EXTERNAL |
| |
| THERMOSTAT | THERMOSTAT | THERMOSTAT IS USED |
|
FOUTLET 210°F OUTLET 240°F OUTLETMAXIMUMTEMPERATURE
G | 190°F | 220°F | MAX. |
H | DEGREES°F | DEGREES°C | EITHER °F OR °C FOR DISPLAYED |
|
|
| TEMPERATURE |
Figure 2. Summary of Dip Switch Options.
DIFFERENTIAL PRESSURE SWITCH
The differential pressure switch ensures that a sufficient differential exists between the air pressure in the
This differential pressure switch is normally open and closes when the combustion blower starts.
BLOCKED FLUE PRESSURE SWITCH
The blocked flue pressure switch ensures that the flue gas vent is clear. This pressure switch is normally closed and only opens on the fault conditions.
FLAME SENSOR
The flame sensor acts to prove the flame has carried over from the ignitor to the
WATER FLOW SWITCH
The Water Flow Switch is installed at the boiler outlet to prevent burner operation in the event of inadequate water flow through the boiler. The Water Flow Switch is a single pole, normally open switch that will close its contacts when increasing water flow rate is encountered. This switch is
LIMIT CONTROLS
CAUTION
LIMIT CONTROLS ARE SAFETY DEVICES AND ARE NOT TO BE USED AS A THERMOSTAT.
The GB/GW models incorporate an outlet water probe consisting of two limit controls:
1.An adjustable automatic reset limit control, that can be set to either 210°F (99°C) or 240°F (115°C) depending on the application.
2.A fixed manual reset limit factory set at 250°F (121°C). If the manual reset should open due to high temperature the gas valves will close and the unit will go into lockout.
If lockout occurs, manually push the ENTER/RESET
ON/OFF SWITCH
The ON/OFF switch is a
COMBUSTION AIR BLOWER
Provides air for combustion process. The blower settings are adjustable through the use of the air shutter, however, blowers are set at the factory and should not need adjustment.
TANK PROBE
FOR HOT WATER SUPPLY SYSTEMS (GW models), A tank probe is supplied with each hot water supply boiler. The inlet water temperature will default to the tank temperature on the display when the tank probe is installed.
Note: Tank Probe must be designated as controlling probe using Dip Switch "D" on Central Control Board before it can be used for (GW) hot water supply applications.
"Pigtails" of
FOR HOT WATER HEATING SYSTEMS (GB models) Due to the
many various types of systems and operating conditions, a tank