Table 19. Error Code Chart

GENESIS II CONTROL - FAULT OPERATION

 

FAULT

ERROR CODES

LOCKOUT

 

COMMUNICATIONS FAULT (CCB TO ICB)

 

 

 

 

STAGE 1:

001

HARD

 

STAGE 2:

002

HARD

 

STAGE 3:

003

HARD

 

STAGE 4:

004

HARD

 

 

 

 

 

 

ECO/HIGH LIMIT:

010

HARD

 

NO GAS VALVE POWER SENSED

011

HARD

 

STAGE 1:

 

STAGE 2:

012

HARD

 

STAGE 3:

013

HARD

 

STAGE 4:

014

HARD

 

LWCO

020

HARD

 

CIRCULATE FAULT (FLOW SWITCH)

030

SOFT

 

 

 

 

 

 

INSUFFICIENT AIR (AIR PRESSURE SWITCH)

 

 

 

 

STAGE 1:

041

SOFT

 

STAGE 2:

042

SOFT

 

STAGE 3:

043

SOFT

 

STAGE 4:

044

SOFT

 

BLOCKED FLUE

060

SOFT

 

POWER VENT

070

SOFT

 

 

 

 

 

 

IGNITER FAILURE

 

 

 

 

STAGE 1:

081

HARD

 

STAGE 2:

082

HARD

 

STAGE 3:

083

HARD

 

STAGE 4:

084

HARD

 

LOW GAS FAILURE

090

HARD

 

 

 

 

 

 

HIGH GAS FAILURE

 

 

 

 

STAGE 1:

101

HARD

 

STAGE 2:

102

HARD

 

STAGE 3:

103

HARD

 

STAGE 4:

104

HARD

 

 

 

 

 

 

GAS VALVE RELAY FAILURE

 

 

 

 

STAGE 1:

111

HARD

 

STAGE 2:

112

HARD

 

STAGE 3:

113

HARD

 

STAGE 4:

114

HARD

 

 

 

 

 

 

FLAME FAILURE

 

 

 

 

STAGE 1:

121

HARD

 

STAGE 2:

122

HARD

 

STAGE 3:

123

HARD

 

STAGE 4:

124

HARD

 

 

 

 

 

 

PROBE FAULTS

 

 

 

 

OUTLET PROBE

131

HARD

 

INLET PROBE

132

HARD

 

REMOTE PROBE

133

HARD

 

IRI GAS VALVE FAILURE

140

HARD

 

CPU FAULT

210

HARD

For additional information please refer to the User’s Manual supplied with the boiler or contact: