1.Press the SELECT
2.The LED display will show the current
3.Press and hold the ADJUST
4.When the desired
5.Press the ENTER/RESET
6.The appliance will now control the temperature to the desired
7.For setting the stage differentials, see the section labeled Procedure for Setting Stage Differential.
NOTE: The boiler must complete a full cycle in order for the new setting to take effect. If the unit is turned off prior to a complete cycle the setting will be lost and the previous setting will remain in effect.
24 VAC System Controller (Optional)
A 24 VAC thermostat/aquastat can be implemented as a system controller on Genesis units. The connection for such devices is located in the 24 VAC junction box at the rear of the unit. A 24 VAC thermostat/aquastat can only be used as an "On/Off" switch for the unit. The actual controlling of the staging will be through either the inlet or tank probe. To use a 24 VAC system controller, dip switch "E" on the CCB must be switched to the "on" position. See Figure 14.
Tank Probe (Optional)
In addition to the Inlet and Outlet/ECO Probes, units can be optionally equipped with a tank Probe. The connection for the tank probe is located in the 24 VAC junction box at the rear of the unit. The tank Probe can be configured to control the staging of the unit. See Tank Probe Installation section on page 17 for additional information.
Procedure for Setting Tank Probe Temperature
If you have a GW hot water supply boiler, and have installed the tank probe, below are the instructions on how to adjust the water temperature
1.Press the SELECT
2.The LED display will show the current
3.Press and hold the ADJUST
4.When the desired
5.Press the ENTER/RESET
6.The appliance will now control the temperature to the desired
7.For setting the stage differentials, see the section labeled Procedure for Setting Stage Differential.
Procedure for Setting Stage Differential
Once the system control and
be established. To facilitate proper operation and maximize appliance performance, each stage has a programmable operating switching differential or “hysteresis” about the set point. This means a call for heat for a particular stage will become active when the water temperature measured at the controlling temperature sensing probe drops to the
To change or view the current programmed switching differential:
1.Press the SELECT
2.The LED display will show the current differential for stage one.
3.Press and hold the ADJUST
4.When the desired
5.Press the ENTER/RESET
6.Repeat steps 2 through 5 for the rest of the stages.
7.The appliance will now control temperature utilizing the desired differentials.
Example:
Application: Hydronic Heating
Desired System Temperature: 185°F (85°C)
Stage Differentials: 5°F (3°C) per Stage.
Note: The user must first choose which probe is to control the staging of the unit. The controlling probe will be either the inlet or tank probe. (If the tank probe is used to regulate loop temperature in hydronic applications (GB Models), make sure it is located on the return side of the closed loop.) Use Dip Switch "D" on the Central Control Board to make this selection. See Figure 14.
Set the stage differentials using the procedure described in the Procedure for Setting Stage Differential section of the document. Setting the control as described in the above example (5°F differentials for each stage) will give the following stage
Stage One
Off Temperature: 185°F (85°C)
On Temperature: 180°F (82°C)
Stage Two
Off Temperature: 180°F (82°C)
On Temperature: 175°F (79°C)
Stage Three
Off Temperature: 175°F (79°C)
On Temperature: 170°F (77°C)
Stage Four
Off Temperature: 170°F (77°C)
On Temperature: 165°F (74°C)
29