GAS CONNECTIONS

WARNING

THIS BOILER IS NOT INTENDED TO OPERATE AT GAS SUPPLY PRESSURE OTHER THAN SHOWN ON THE RATING PLATE. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO GAS VALVES WHICH CAN RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVES MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE BOILER. VENT BLOCKAGE MAY OCCUR DURING ICE BUILD-UP OR SNOW STORMS.

WHEN LOCAL CODES REQUIRE A MAIN MANUAL SHUT-OFF VALVE OUTSIDE THE BOILER JACKET,ASUITABLE MAIN MANUAL SHUT-OFF VALVE MUST BE INSTALLED IN A LOCATION COMPLYING WITH THOSE CODES.

threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.

THE BOILER MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS MAIN MANUAL GAS SHUT-OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR MORE THAN 1/2 PSIG.

1.CORRECT GAS - Make sure gas on which the boiler will operate is the same as that specified on the rating plate. Do not install the boiler if equipped with a different type of gas. Consult your gas supplier.

2A. SIZING GAS SUPPLY LINE (For single boiler installations). See table 15.

2B. SIZING GAS SUPPLY LINE (For multiple installations of two or more boilers). See tables 13 (Natural Gas) and 14 (Propane Gas).

IT IS IMPORTANT TO GUARDAGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION. IF COPPER SUPPLY LINES ARE USED THEY MUST BE APPROVED FOR GAS SERVICE.

BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG) MUST BE INCORPORATED IN THE PIPING. THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH RECOM- MENDATIONS OF SERVING GAS SUPPLIERS. REFER TO NATIONAL FUEL GAS CODE, ANSI Z223.1 OR CAN/CSA -B149.1 AND .2 (AND LATEST ADDENDA).

Gas Pipe sizing may be larger than heater connections on installations where a significant run of piping is required. To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas inlet.

Fittings and unions in the gas line must be metal to metal type.

Apply joint compounds (pipe dope) sparingly and only to the male

TABLE 15. SINGLE UNIT INSTALLATION, SUGGESTED PIPE SIZE

DISTANCE FROM METER

BTU INPUT

0-50'

51-100'

101-200'

201-300'

301-500'

 

990,000

2"

2"

2 1/2"

2 1/2"

2 1/2"

 

1,300,000

2"

2 1/2"

2 1/2"

3"

3"

 

1,500,000

2"

2 1/2"

3"

3"

3 1/2"

 

1,850,000

2 1/2"

2 1/2"

3"

3"

3 1/2"

 

2,100,000

2 1/2"

3"

3"

3 1/2"

4"

 

2,500,000

2 1/2"

3"

4"

4"

4 1/2"

 

 

 

 

 

 

 

 

Use tables 13 or 14, which are taken from ANSI booklet Z223.1, NATIONAL FUEL GAS CODE, or CAN/CSA-B149.1and .2 (and latest addenda) to size iron pipe or equivalent gas supply line. Table 13 is based on a pressure drop of 0.5 inches of water and a specific gravity of 0.60 approximately that of natural gas. (LP gas has an S.G. of about 1.53). If the service pressure is five inches water column or less, use one pipe size larger than specified in tables 13-15 in order to minimize pressure drop in the line.

No additional allowance is necessary for an ordinary number of fittings. Where it is necessary to use more than the average number of pipe fittings i.e. elbows, tees, and valves in gas supply line, use a pipe larger than specified to compensate for increased pressure drop.

TABLE 16. Orifice Size for Natural and Propane (LP) Gases (U.S. and Canadian Installations) [Drill size unless otherwise indicated.]

 

Rating Input

Number of

 

 

Model

BTUH

Burners

Natural (Holes)

Propane (Holes)

GB/GW 1000

990,000

10

0.111" (4X)

0.071" (3X)

GB/GW 1300

1,300,000

13

0.111" (4X)

0.071" (3X)

GB/GW 1500

1,500,000

15

0.111" (4X)

0.071" (3X)

GB/GW 1850

1,850,000

19

0.111" (4X)

0.071" (3X)

GB/GW 2100

2,100,000

21

0.111" (4X)

0.071" (3X)

GB/GW 2500

2,490,000

25

0.111" (4X)

0.071" (3X)

21

Page 21
Image 21
A.O. Smith 1300, 200 GAS Connections, Single Unit INSTALLATION, Suggested Pipe Size, Distance from Meter BTU Input, Btuh