41 U104613-03

Read all instructions before installing or using this appliance.
Installation Instructions
Save these instructions for future reference.
F Connect flexible metal appliance connector
to the adapter on the range. Position range to
permit connection at the shut-off valve.
G When all connections have been made, make
sure all range controls are in the off position
and turn on the main gas supply valve. Use a
liquid leak detector at all joints and connections
to check for leaks in the system. Use a product
specifically manufactured for leak detection.
Leak testing of the appliance shall be conducted
in accordance to the manufacturers instructions.
H Refit upper section of the extractor air box duct.
Fit splash back panel (if required) to flue grill and
refit the flue grill to the range.

CAUTION: DO NOT USE A FLAME TO

CHECK FOR GAS LEAKS.

When using test pressures greater than 1/2 psig
(3.5kPa) to pressure test the gas supply system of
the residence, disconnect the range and individual
shut-off valve from the gas supply piping. When
using test pressures of 1/2 psig (3.5kPa) or less
to test the gas supply system, simply isolate the
range from the gas supply system by closing the
individual shut-off valve.Flexible Connector
Installer: Inform the consumer of the location of
the gas shut-off valve.
Electrical Connection

When installed the range must be electrically

grounded in accordance with local codes

or; in the absence of local codes with the

National Electrical Code ANSI/NFPA 70, latest

edition.

In Canada the range must be installed in

accordance with the current CSA Standard

C22.1 - Canadian Electrical Code Part 1.

Electrical Power Supply Requirements

Electrical Requirements
CAUTION: FOR PERSONAL SAFETY, DO NOT USE AN
EXTENSION CORD WITH THIS APPLIANCE. REMOVE
HOUSE FUSE OR OPEN CIRCUIT BREAKER BEFORE
BEGINNING INSTALLATION.
This appliance must be supplied with the proper
voltage and frequency, and connected to an
individual, properly grounded branch circuit,
protected by a circuit breaker or time-delay fuse, as
noted on the rating plate.
Wiring must conform to National Electric Codes.
If the electric service provided does not meet the
above specifications, have a licensed electrician
install an approved outlet.
Because range terminals are not accessible after
range is in position, flexible service conduit or cord
must be used.

Provide Proper Elec trical Supply

This range must be supplied with 208/240 volt,
60 Hz., and connected to an individual, properly
grounded branch circuit protected by a circuit
breaker or time-delay fuse (40 amp). The receptacle
must be NEMA 14-50R to accept the 4-prong plug
supplied with the range.
If the electrical service provided does not meet
the above specifications, it is recommended that a
licensed electrician install an approved outlet.
Locate the electric supply as illustrated.
Recommended acceptable electrical outlet area. Orient the electrical receptacle
so the length is parallel to the floor.