Alliance Laundry Systems 9001889R7 manual Inverter Drive Error Codes, Operation, Name, Check point

Models: 9001889R7

1 62
Download 62 pages 8.61 Kb
Page 60
Image 60
During acceleration–If a current of more

Inverter Drive Error Codes

Operation

Name

Description and NOTES

Check point

Corrective action

Panel

Indication

 

 

 

 

 

 

 

 

 

Stall prevention

During acceleration–If a current of more

Check to make sure

Load the machine

 

(overcurrent)

than 150% of the rated inverter current

the machine is

properly to

 

 

flows in the motor this function stops the

loaded properly and

distribute the load

 

 

increase in frequency until the overload

that the load is

evenly.

 

 

current reduces to prevent the inverter

balanced.

Contact Alliance

 

 

from resulting in overcurrent shut-off.

Verify that the AC

Laundry Systems’

 

 

When the overload current has reduces

drive’s parameters

Customer Service

 

 

are correct.

department.

 

 

below 150%, this function increases the

 

 

 

 

 

 

 

 

frequency again.

 

 

 

 

 

 

During constant-speed operation–If a

 

 

 

 

 

 

current of more than 150%, this function

 

 

 

 

 

 

lowers the frequency again.

 

 

 

 

 

 

When the overload current has reduces

 

 

 

 

 

 

below 150%, this function increases the

 

 

 

 

 

 

frequency again.

 

 

 

 

 

 

During deceleration–If a current of more

 

 

 

 

 

 

than 150% of the rated inverter current

 

 

 

 

 

 

flows in the motor, this function stops the

 

 

 

 

 

 

decrease in frequency until the overload

 

 

 

 

 

 

current reduces to prevent the inverter

 

 

 

 

 

 

from resulting in overcurrent shut-off.

 

 

 

 

 

 

When the overload current has reduced

 

 

 

 

 

 

below 150%, this function decreases the

 

 

 

 

 

 

frequency again.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stall prevention

During deceleration-If the regenerative

Check to make sure

Load the machine

 

(overvoltage)

energy of the motor exceeds the brake

the machine is loaded

properly to distribute

 

 

capability, this function stops the decrease

properly and that the

the load evenly.

 

 

in frequency to prevent overvoltage

load is balanced.

 

 

 

shutoff. As soon as the regenerative

 

 

 

 

 

 

energy has reduced, deceleration resumes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PU stop

A stop made by pressing the

STOP

key of

Check for a stop made

Perform operation

 

RESET

 

 

the PU has been set in Pr. 75 “PU stop

by pressing the

STOP

 

correctly.

 

 

RESET

 

 

selection”.

key of the operation

 

 

 

 

 

 

panel during external

 

 

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

 

 

This alarm appears if:

 

 

 

Perform operation

 

 

The RES signal is on;

 

 

 

correctly.

 

 

You attempted to set any parameter

 

 

 

 

 

 

value in the external operation mode;

 

 

 

 

 

 

You attempted to change the operation

 

 

 

 

 

 

mode during operation;

 

 

 

 

 

 

You attempted to set any parameter

 

 

 

 

 

 

value outside its setting range.

 

 

 

 

 

 

You attempted to set any parameter

 

 

 

 

 

 

value during operation (while signal

 

 

 

 

 

 

STF or STR is ON).

 

 

 

 

 

 

You attempted to set any parameter

 

 

 

 

 

 

value while parameter write is being

 

 

 

 

 

 

inhibited in Pr. 77 “parameter write

 

 

 

 

 

 

inhibit selection”.

 

 

 

 