Installation

Electrical Plug Connection

Three-Wire Plug

NOTE: The power cord (pigtail) is NOT supplied with the electric dryer. Type of pigtail and gauge of wire must conform to local codes and instructions.

The method of wiring the dryer is optional and subject to local code requirements.

POWER SUPPLY

POWER SUPPLY

1 2

NOTE: Connect the dryer to the power supply with the MAXIMUM RATED VOLTAGE listed on the nameplate.

A typical

INTERMEDIATE

30-Amp

FUSE BOX (May

Three-wire

be omitted if

Receptacle

service entrance

NEMA Type

box is fused)

10-30R

 

WALL RECEPTACLE

120 ± 12

120 ± 12

V.A.C.

V.A.C.

 

 

240 ± 12

 

V.A.C.

3

INTERMEDIATE SHUT-OFF BOX (May or may not be fused)

4

5 6

NOTE: Use COPPER WIRE only. k

 

L1 L2

7

L1 L2

 

 

 

Shorter than 15k (4.5 m) use 10 A.W.G.

PIGTAIL CONNECTION

 

DIRECT CONNECTION

 

Longer than 15k (4.5 m) use 8 A.W.G.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D816I

1

3-Wire Grounded Neutral 120/240 Volt, 60 Hertz

4

Metallic or Non-Metallic Sheathed Cable

 

AC 1 Phase Service Entrance Switch Box

 

 

(Copper wire only)

 

 

 

(See NOTE above)

 

5

Pigtail to Dryer (See NOTE above)

2

30 Ampere Fuses or Circuit Breaker

 

6

Neutral

 

 

3

Neutral Wire

 

7

Terminal Block in Dryer

 

 

1. Remove access cover from rear of dryer.

Figure 26

2.Use a strain relief and insert end of power cord through power supply hole.

D695I

Figure 27

D696I

Figure 28