Amana ARR6102, ART6112, ART6002, ARR6202 Installing 3-WirePower Cord, Power terminals, Ai B

Models: ARR6102 ARR6202 ART6002 ART6112

1 28
Download 28 pages 5.78 Kb
Page 7
Image 7
Power terminals

Range has been grounded at the factory to the center (nickel plated) terminal of the terminal block in accordance with the National Electrical Code (section 2560). When a separate ground is required by local code, disconnect the grounding strap from the terminal block. Ground frame by connecting a grounding wire to range frame using only the grounding screw removed from the grounding strap.

Neutral terminal connect wire with white insulation

Power terminals

(240 V)

\

Ground

strap

Power lead connect wire with black or red insulation and brass terminal

Terminal Block

Installing 3-Wire Power Cord

Refer to power cord instructions if available for additional information.

1.Remove rear wire cover on rear of range.

2.Place strain relief (winged clamp) in cord access hole below terminal block.

Strain relief is supplied with cord. Place wings through hole, entering from bottom. Screw holes in clamp should be below mounting panel. Place cord through strain relief.

3.Attach neutral (center) or white wire to center terminal on terminal block.

4.Attach power lead, red wire or black wire to left side power terminal.

5.Attach power lead, red wire or black wire to the right side power terminal.

6.Afterwires have been placed on terminals, attach with hex nuts provided.

Firmly tighten to ensure proper electrical connection.

7.Place screw through strain relief and tighten.

8.Replace rear wire cover.

Wires from range

(Number of wires on each terminal can vary)

AI B

A

Terminal block is approved for copper wire connection

only, NOT aluminum wiring. If aluminum house wiring is to be connected, the following procedure is suggested.

1.Connect length of copper building wire to range terminal block with ring terminals.

2.Splice copper wires to aluminum wiring using connectors which are designed certified by Underwriter's Laboratories and recognized for joining copper to aluminum. Follow the connector manufacturer's recommended procedure.

3.Wire used, location and enclosure of splices must conform to local codes.

Wires from power cord

APower lead tenninal (Connect black o1"red insulated wire and secure with brass nut.)

BNeutral terminal (Connect insulated white insulated wire and secure with brass nut.)

Installing 3-wire Power Cord

Page 7
Image 7
Amana ARR6102, ART6112, ART6002, ARR6202 owner manual Installing 3-WirePower Cord, Power terminals, Ai B