INSTALLATION EXAMPLES (CONT'D)

Example diagram only-duct configuration may change depending on model

DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and

EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN

Simplified Installation

Option 1

(Return/Return Method)

• HRV must be balanced

• It is mandatory that the furnace blower run continuously or HRV operation

be interlocked with the furnace blower

• Check local codes/authority having jurisdiction for acceptance

Note: Option 1 is the pre- ferred/recommended method when doing a simplified installation

* Ducts connection may

Return Air

 

vary depending on model

 

 

 

 

40”

1 m

Outdoors

Min.

(3’-3”) min.

 

 

recommended

 

 

 

 

Cool Air

 

NOTES:

Return

 

 

1.Furnace blower may be required to operate when ventilation from HRV/ERV is required. The furnace should be set to run continuously or interlocked with HRV/ERV.

2.A minimum separation of 39 inches (1m) is recommended between the two direct connections.

3.The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.

4.Weatherhood arrangement is for drawing purposes only. 6’ (2m) minimum separation recommended. 18” (460 mm) above grade minimum.

5.Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the HR/ERV’s airflow must be confirmed on site, using the balancing procedure found in the installation manual.

*Unit is normally balanced on HIGH speed with furnace blower ON.

18

Page 18
Image 18
Amana HRV-300D, HRV-200 manual Simplified Installation, Option Return/Return Method, Be interlocked with the furnace blower