Amana HRV-150D, HRV-200D, HRV-300D manual Option Supply/Return Method

Models: HRV-200 HRV-300D HRV-200D HRV-150 HRV-150D

1 28
Download 28 pages 56.01 Kb
Page 19
Image 19

INSTALLATION EXAMPLES (CONT'D)

Example diagram only-duct configuration may change depending on model

DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM &

EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE

Simplified Installation

Option 2

(Supply/Return Method)

• HRV must be balanced

• It is recommended that the furnace blower run continuously or HRV operation

be interlocked with the furnace blower

• Check local codes /authority having jurisdiction for acceptance

Note: Option 1 is the pre- ferred/recommended method when doing a simplified installation

* Ducts connection may

Return Air

 

 

 

 

 

vary depending on model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1m

Outdoors

 

 

 

 

 

(3’-3”) min.

 

 

 

 

 

 

 

 

 

recommended

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool Air

Return

NOTES:

1.Furnace blower may be required to operate when ventilation from HRV/ERV is required. The furnace should be set to run continuously or interlocked with HRV/ERV.

2.The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.

3.Weatherhood arrangement is for drawing purposes only. Six feet (2m) minimum separation recommended. Eighteen inches (460 mm) above grade minimum.

4.Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the HR/ERV’s airflow must be confirmed on site, using the balancing procedure found in the installation manual.

1 m

(3’-3”) min.

recom-

mended

* Unit is

normally

balanced

on HIGH

speed

with

furnace

blower

ON.

19

Page 19
Image 19
Amana HRV-150D, HRV-200D, HRV-300D manual Option Supply/Return Method