WARNING: If the water in the supply line or water solenoid valve freezes, the fire suppression system will be INOPERATIVE!!
The manual ball cock shutoff valve must be located outside of the dryer at a distance from the dryer where it is easily accessible.
3.Electrical Requirements
No independent external power source or supply connection is necessary. The
WARNING: Electrical power must be provided to the dryer at ALL times. If the main electrical power supply to the dryer is disconnected, the fire suppression system is
INOPERATIVE!!
FIRE SUPPRESSION SYSTEM THEORY OF OPERATION
While the dryer is in an idle state, or
While a drying cycle is in process and the heat has turned on at least once, the microprocessor controller (computer) monitors the exhaust temperature transducer. If the drying cycle temperature set point is set greater than 160° F (71° C) and the microprocessor controller (computer) detects an exhaust temperature rise 25° F greater than set point, this will be the trip point and the fire suppression system routine will activate. If set point is below 160° F (71° C), the trip point will be 185° F (85° C).