American Dryer Corp MD-170PTVW, MDG-120PVV installation manual Multiple Dryer Common Venting

Models: MD-170PTVW

1 52
Download 52 pages 9.4 Kb
Page 20
Image 20
4. Multiple Dryer (Common) Venting

4. Multiple Dryer (Common) Venting

IMPORTANT: For extended ductwork runs, the cross-sectional area of the ductwork can only be increased to an extent. When the ductwork approaches the maximum limits as noted in this manual, a professional heating, ventilating, and air-conditioning (HVAC) firm should be consulted for proper venting information.

If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be channeled into a “common main duct.” The individual ducts should enter the bottom or side of the main duct at an angle not more than 45º in the direction of airflow. The main duct should be tapered, with the diameter increasing before each individual duct is added.

IMPORTANT: No more than 4 dryers for the MDG-120 and only 3 for the MD-170 should be connected to 1 main common duct.

The illustration below shows the minimum cross-sectional area for multiple dryer round or square venting. These figures must be increased if the main duct run from the last dryer to where it exhausts to the outdoors is longer than 12 feet (3.656 meters) or has more than 1 elbow in it.

A = MDG-120 14-inch (35.56 cm)

MDG-170 18-inch (45.72 cm)

MDS-170 20-inch (50.8 cm)

B = 20 feet (6.10 meters)

NOTE 1 Opening from combustible materials must be 2-inches (5.08 cm) larger than the duct (all the way around). The duct must be centered within this opening.

NOTE 2 Distance should be 2 times the diameter of the duct to the nearest obstruction.

Multiple Dryer Venting with 14-inch (35.56 cm) Diameter

2,150 cfm (60.88 cmm) Exhaust Connections at Common Duct

 

 

 

MDG-120

NUMBER OF DRYERS

4

 

3

2

 

1

 

 

 

 

 

 

 

 

MINIMUM CROSS-

SQ IN

455

 

380

255

 

115

 

 

 

 

 

 

 

 

SECTIONAL AREA

SQ CM

2935

 

2452

1645

 

742

 

 

 

 

 

 

 

 

MINIMUM ROUND

IN

24

 

22

18

 

14

 

 

 

 

 

 

 

 

DUCT DIAMETER

CM

60

 

55

45

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multiple Dryer Venting with 18-inch (45.72 cm) Diameter

 

 

 

Multiple Dryer Venting with 20-inch (50.8 cm) Diameter

3,700 cfm (104.77 cmm) Exhaust Connections at Common Duct

 

4,400 cfm (124.59 cmm) Exhaust Connections at Common Duct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

170-MDG

NUMBER OF DRYERS

 

3

2

 

1

 

 

170-MDS

 

NUMBER OF DRYERS

3

2

1

 

MINIMUM CROSS-

SQ IN

 

615

455

 

255

 

 

 

MINIMUM CROSS-

SQ IN

707

531

315

 

 

SECTIONAL AREA

SQ CM

 

3967

2935

 

1645

 

 

 

 

SECTIONAL AREA

 

 

 

 

 

 

 

 

 

 

SQ CM

4561

3426

2032

 

 

 

IN

 

28

24

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM ROUND

 

 

 

 

 

 

MINIMUM ROUND

IN

30

26

20

 

 

DUCT DIAMETER

CM

 

71

61

 

46

 

 

 

 

DUCT DIAMETER

CM

76

66

51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

Maytag Co.

113395 - 6

Page 20
Image 20
American Dryer Corp MD-170PTVW, MDG-120PVV installation manual Multiple Dryer Common Venting