ON-BATTERY OPERATION

The Smart-UPS switches to battery operation automatically if the utility power fails. While running on-battery, an internal alarm sounds (periodic beeps).

Press the button (front panel) to silence the UPS alarm (for the current alarm only). You can change the audible indicator if you are using the PowerChute software.

If the utility power does not return, the UPS continues to supply power to the connected equipment until exhausted. The UPS will begin to beep continuously approximately two minutes before the UPS final low battery shutdown. If using a computer, you must manually save your files and power down before the UPS turns off, unless you are using PowerChute interface software that provides auto- matic, unattended shutdown.

DETERMINING ON-BATTERY RUN TIME

UPS battery life differs based on usage and environment. It is recommended that the battery/batteries are changed once every three years.

Although the following run times are “typical,” these numbers are subject to change. For the most recent and accurate sizing information, please consult the Size-UPS section of APC’s website at www.apc.com/sizing.

LOAD (VA)

LOAD (WATTS)

RUN TIME (MINUTES)

750

600

40m

 

 

 

1125

900

25m

 

 

 

1500

1200

16m

 

 

 

2200

1750

11m

 

 

 

2500*

2000*

9m

3000*

2400*

7m

*Runtimes at these load levels are applicable to the SU3000RMXL3U only.

For non-power factor corrected loads, the power in watts may be limited by the maxi- mum VA rating.

14

Page 16
Image 16