NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
High Transfer | 120V Models | 120V Models | To avoid unnecessary battery usage, set | |
Point | 132 VAC | 138, 135, 129 VAC | the high transfer point higher if the | |
| 230V Models | 230V Models | utility voltage is chronically high and | |
| 253 VAC | 264, 271, 280 VAC | the connected equipment is known to | |
|
|
| work under this condition. | |
|
|
|
| |
Low Transfer | 120V Models | 120V Models | Set the low transfer point lower if the | |
Point | 103 VAC | 97, 100, 106 VAC | utility voltage is chronically low and | |
| 230V Models | 230V Models | the connected equipment can tolerate | |
| 196 VAC | 188, 204, 208 VAC | this condition. | |
|
|
|
|
16