4: USER CONFIGURATION ITEMS
NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.
FUNCTION FACTORY
DEFAULT
USER SELECTABLE
CHOICES DESCRIPTION
Automatic Self-
Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
On Startup Only,
No Self-Test
This function sets the interval at which
the UPS will execute a self-test. Refer
to your software manual for details.
UPS ID UPS_IDEN Up to eight char-
acters to define
the UPS
Use this field to uniquely identify the
UPS for network management pur-
poses.
Date of Last Bat-
tery Replacement
Manufacture
Date
Date of Battery
Replacement
Reset this date when you replace the
battery module.
Minimum Capac-
ity Before Return
from Shutdown
0 percent 15, 50, 90 percent The UPS will charge its batteries to the
specified percentage before return from
a shutdown.
Sensitivity Normal Reduced, Low Set lower than normal sensitivity to
avoid lowered battery capacity and
service life in situations where the con-
nected equipment can tolerate minor
power disturbances.
Duration of Low
Battery Warning
2 minutes 5, 7, 10 minutes This function sets the time before shut-
down at which the UPS issues a low
battery warning. Set it higher than the
default if the operating system needs
more time for shutdown.
Alarm Delay
After Line Fail
5 second delay 30 second delay,
At Low Battery
Condition,
No Alarm
Set the alarm delay to avoid alarms for
minor power glitches.
Shutdown Delay 20 seconds 0, 80, 300, 600
seconds
This function sets the interval between
when the UPS receives a shutdown
command and when shutdown occurs.
Synchronized
Turn-on Delay
0 seconds 60, 180, 300 sec-
onds
The UPS will wait the specified time
after the return of utility power before
turn-on (for example, to avoid branch
circuit overload).