4:USER CONFIGURATION ITEMS

NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

Automatic Self-

Every 14 days

Every 7 days

This function sets the interval at which

Test

(336 hours)

(168 hours),

the UPS will execute a self-test. Refer

 

 

On Startup Only,

to your software manual for details.

 

 

No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight char-

Use this field to uniquely identify the

 

 

acters to define

UPS for network management pur-

 

 

the UPS

poses.

 

 

 

 

Date of Last Bat-

Manufacture

Date of Battery

Reset this date when you replace the

tery Replacement

Date

Replacement

battery module.

 

 

 

 

Minimum Capac-

0 percent

15, 50, 90 percent

The UPS will charge its batteries to the

ity Before Return

 

 

specified percentage before return from

from Shutdown

 

 

a shutdown.

 

 

 

 

Sensitivity

Normal

Reduced, Low

Set lower than normal sensitivity to

 

 

 

avoid lowered battery capacity and

 

 

 

service life in situations where the con-

 

 

 

nected equipment can tolerate minor

 

 

 

power disturbances.

 

 

 

 

Duration of Low

2 minutes

5, 7, 10 minutes

This function sets the time before shut-

Battery Warning

 

 

down at which the UPS issues a low

 

 

 

battery warning. Set it higher than the

 

 

 

default if the operating system needs

 

 

 

more time for shutdown.

 

 

 

 

Alarm Delay

5 second delay

30 second delay,

Set the alarm delay to avoid alarms for

After Line Fail

 

At Low Battery

minor power glitches.

 

 

Condition,

 

 

 

No Alarm

 

 

 

 

 

Shutdown Delay

20 seconds

0, 80, 300, 600

This function sets the interval between

 

 

seconds

when the UPS receives a shutdown

 

 

 

command and when shutdown occurs.

 

 

 

 

Synchronized

0 seconds

60, 180, 300 sec-

The UPS will wait the specified time

Turn-on Delay

 

onds

after the return of utility power before

 

 

 

turn-on (for example, to avoid branch

 

 

 

circuit overload).

 

 

 

 

15