Wiring Under the Floor
A licensed electrician must route and connect the power cables for
Electrical
Hazard
Make sure all wire connections and circuit breaker connections are properly torqued.
Warning
If you are routing power cables to the enclosures under a raised floor, you must provide the appropriate power cables and equipment for installation, and a licensed electrician must route and connect the power cables to the PDU circuit breakers. To wire each power cable to an enclosure:
1.Push out a
2.Install Liquidtite™ waterproof conduit under the floor from each enclosure to the PDU.
3.From the Rack PDU or Rack ATS in each enclosure, thread the appropriate power cable (for your application) from the enclosure through the Liquidtite conduit to the PDU.
4.At the PDU, route the cable through the opening you created in step 1 and then up through the wireway () at either side of the PDU. This will allow you to connect cable to the upper circuit breaker panel.
30 | InfraStruXure |