American Power Conversion 60kW InfraStruXureTM System manual Heat Output

Models: 60kW InfraStruXureTM System

1 60
Download 60 pages 33.19 Kb
Page 16
Image 16

Heat Output

Consider the heat dissipation ratings of equipment to determine cooling requirements. Additional cooling equipment may be required. Heat output of the InfraStruXure PDU is shown below.

 

Voltage

 

 

 

 

InfraStruXure PDU with a transformer

208V input

7169 BTU/hr

 

 

(2.10kW)

 

480V input

7412 BTU/hr

 

 

(2.17kW)

 

600V input

4894 BTU/hr

 

 

(1.43kW)

 

 

 

The heat output is higher while batteries are charging. Under normal operating conditions, battery recharging periods are infrequent.