3.5. DC SYSTEM GROUNDING

The return bus for the power plant must be connected to the Central Office Ground. The left end of the return bus provides a pair of threaded 3/8-16 holes on 1-inch (25.4 m) centers for connection of a two-hole lugged cable to the Master Station Ground. Details for this connection should be provided in the site electrical grounding plans.

Figure 3.5-1 DC Ground Connection Point