American Power Conversion MX28B400 Lamp Test, LVD Option, Disable, LVD Reset, +24.00, LVD Trip

Models: MX28B400

1 52
Download 52 pages 9.84 Kb
Page 33
Image 33

Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Lamp Test

Setting Lamp Test to “ON” will turn on

Lamp Test

m+

Security Level {1}

the “MAJOR”, “MINOR”, “NORMAL”,

OFF

 

[SYSTEM/DIAG]

“MAJ”, and “MIN” LEDs on the control

 

 

 

unit front panel.

 

 

LVD 1 or 2 Option

Must be set to “Enable” if the unit has an

LVD Option

m+

Security Level {1}

LVD. If the unit has an LVD, but it is

Disable

[MODULES/LVD/SET-ALM]

disabled, the controller will not

 

 

 

disconnect the LVD.

 

 

LVD 1 or 2 Reset

LVD Reset (reconnect) threshold voltage.

LVD Reset

m+

Security Level {1}

 

+24.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD 1 or 2 Trip

LVD Trip (disconnect) threshold voltage.

LVD Trip

m+

Security Level {1}

 

+21.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD Alarm

The output relay that is energized when

LVD Open Alm m+

Security Level {1}

the controller opens the LVD. If unit has

Minor

 

[MODULES/LVD/SET-ALM]

a battery LVD, no power will be available

 

 

 

to turn on any Output Relays.

 

 

Model Programming

Model type number for the power plant

Model

m+

Security Level {2}

NOTE: Changing the model number

MX28B-400 +24V

[SYSTEM/SETUP]

causes the system to reinitialize.

 

 

OEM R Gain

Voltage gain adjustment for factory

OEM R Gain

m+

Security Level {2}

calibration of system voltage

1.000 V

[OEM]

readings/settings.

 

 

OEM R Offset

Voltage offset adjustment for factory

OEM R Offset

m+

Security Level {2}

calibration of system voltage

0.000 V

[OEM]

readings/settings.

 

 

OEM S Gain

Current gain adjustment for factory

OEM S Gain

m+

Security Level {2}

calibration of battery current

1.000 A

[OEM]

readings/settings.

 

 

OEM S Offset

Current offset adjustment for factory

OEM S Offset

m+

Security Level {2}

calibration of battery current

0.0 A

[OEM]

readings/settings.

 

 

Output Relay 1 Alarm

Output Relay 1 Alarm can be “mapped”

Out-Rly 1 Alm m+

Security Level {1}

to activate other output relays (“Ignore”

Ignore

 

[SYSTEM/OUT-RLY/RLY-

activates no additional relays).

 

 

MAP]

 

 

 

 

 

 

Output Relay 6 Alarm

Output Relay 6 Alarm can be “mapped”

Out-Rly 6 Alm m+

Security Level {1}

to activate other output relays (“Ignore”

Ignore

 

[SYSTEM/OUT-RLY/RLY-

activates no additional relays).

 

 

 

MAP]

 

 

 

MX28B400 +24 VDC User’s Manual

Page 29

Page 33
Image 33
American Power Conversion MX28B400 Lamp Test, LVD Option, Disable, LVD Reset, +24.00, LVD Trip, +21.00, LVD Open Alm m+