Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Compensation Low Knee

The temperature compensation low knee

Comp Lknee

m+

Security Level {1}

is the point below which there is no

0.0 C

[BATT/COMP]

additional battery voltage compensation

 

 

 

for further decreases in temperature.

 

 

Compensation Method

One of three parameters that control the

Comp Method m+

Security Level {1}

dc output voltage. Activate “ON” or de-

OFF

[BATT/COMP]

activate “OFF” battery temperature

 

 

 

compensation.

 

 

Compensation Temperature

Temperature compensation coefficient

Comp TC

m+

Coefficient

between low knee and high knee in

- 3.00mV

Security Level {1}

mV/cell/°C. (Compensation equals zero

 

 

[BATT/COMP]

at 25°C.)

 

 

Control Unit Revision

Hardware revision level of the control

Cntrl Rev

+

{Status Only}

unit. This parameter cannot be changed.

000002

[SYSTEM/SETUP]

 

 

 

Conv HV Alm

The output relay energized if the

Conv HV Alm

m+

 

Converter Voltage (nominal -48 Vdc) is

Minor

 

above the Converter High Voltage

 

 

 

threshold.

 

 

Conv HV Thr

Converters are an optional device used

Conv HV Thr

m+

 

to convert +24 Vdc to –48 Vdc.

-58.00 V

 

Converter Voltage is converter bus

 

 

 

voltage measured by the controller. An

 

 

 

alarm will be reported if voltage is higher

 

 

 

than the voltage entered.

 

 

Conv LV Alm

The output relay energized if the

Conv LV Alm

m+

 

Converter Voltage (nominal -48 Vdc) is

Minor

 

below the Converter Low Voltage

 

 

 

threshold.

 

 

Conv LV Thr

Converters are an optional device used

Conv LV Thr

m+

 

to convert +24 Vdc to –48 Vdc.

-50.00 V

 

Converter Voltage is converter bus

 

 

 

voltage measured by the controller. An

 

 

 

alarm will be reported if voltage is lower

 

 

 

than the voltage entered.

 

 

Date

Internal system calendar date. Used as

Date

m+

Security Level {1}

a date stamp in the event log.

DEC 16 1999

[SYSTEM/DATE]

 

 

 

Display Type

Type number for the control unit display.

Display Type

+

{Status Only}

This parameter cannot be changed.

000255

[SYSTEM/SETUP]

 

 

 

Fahrenheit Scale

Enables selection of Fahrenheit or

Fahrenheit

m+

Security Level {1}

Celsius temperature scale (Fahrenheit

OFF

[SYSTEM/SETUP]

“OFF” displays readings in °C).

 

 

Firmware Version

Version number of the control unit

FW Version

+

{Status Only}

firmware.

000192

[SYSTEM/SETUP]

NOTE: Actual firmware version

 

 

 

number displayed is the current

 

 

 

version as of the date of manufacture.

 

 

 

This parameter cannot be changed.

 

 

MX28B400 +24 VDC User’s Manual

Page 27

 