Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Output Relay 1 Alias

An alternate name (alias) can be

Out-Rly 1

m+

Security Level {1}

assigned to Output Relay 1 if desired.

Relay 1

 

[SYSTEM/OUT-RLY/ALIAS]

 

 

 

 

 

An alternate name (alias) can be

 

Output Relay 6 Alias {1}

assigned to Output Relay 6 if desired.

Out-Rly 6

m+

[SYSTEM/OUT-RLY/ALIAS]

 

Relay 6

 

Output Relay 1 Delay

Delay between sensing of the alarm

Out-Rly 1 Dly m+

Security Level {1}

condition and activation of Output Relay

0 sec

[SYSTEM/OUT-RLY/RLY-

1. An alarm condition must exist for

 

 

MAP]

longer than the delay to be activated.

 

 

 

 

Delay between sensing of the alarm

 

Output Relay 6 Delay

condition and activation of Output Relay

Out-Rly 6 Dly m+

Security Level {1}

6. An alarm condition must exist for

0 sec

[SYSTEM/OUT-RLY/RLY-

longer than the delay to be activated.

 

 

MAP]

 

 

 

Output Relay Major Alias

An alternate name (alias) can be

Relay Major

 

Security Level {1}

assigned to the major Relay if desired.

m+

 

[SYSTEM/OUT-RLY/ALIAS]

 

Major

 

 

 

 

Output Relay Minor Alias

An alternate name (alias) can be

Relay Minor

 

Security Level {1}

assigned to the Minor Relay if desired.

m+

 

[SYSTEM/OUT-RLY/ALIAS]

 

Minor

 

 

 

 

PIN 1 change

Permanently change password (PIN) that

PIN

m+

Security Level {2}

permits security Level 1 parameter

 

 

[SYSTEM/SETUP]

changes - limited access.

1111

 

 

 

 

PIN 2 Change

Permanently change password (PIN) that

PIN 2

m+

Security Level {2}

permits security Level 2 parameter

 

 

[SYSTEM/SETUP]

changes - unlimited access.

2222

 

 

 

 

PIN Entry

Screen for entry of the active password

PIN

m+

Security Level {0}

(PIN). Before any changes can be

0000

[PIN]

made, the correct pin for the desires

 

 

 

security level must be entered. Level 0 –

 

 

 

full read access. Level 1 –full read and

 

 

 

limited write access. Level 2 – full read

 

 

 

and write access.

 

 

Rectifier Communications Fail

The maximum rectifier communications

RectFailComm

m+

Timeout

response time allowed before a

1 min

Security Level {1}

communications failure is declared.

 

 

[MODULES/RECT/PARAM]

 

 

 

Rectifier Configuration Alarm

The output relay energized if the rectifier

Rect Cfg Alm

m+

Security Level {1}

configuration differs from its stored

Minor

 

[SYSTEM/SET-ALM]

configuration. This occurs if a rectifier is

 

 

 

added after configuration.

 

 

MX28B400 +24 VDC User’s Manual

Page 30